System bus (CAN) with Servo PLC & Drive PLC
System blocks
6.6
CAN_Synchronization
6-21
L
PLC-Systembus EN 1.1
Synchronisation cycle
The controllers/PLCs receive the Sync telegram/signal and compare the time between two LOW-
HIGH edges of the signal to the set cycle time (C1121).
Code
LCD
Possible settings
IMPORTANT
Lenze Choice
[C1121] Sync cycle
2
1
{1 msec}
13
Synchronisation cycle
Definition of the cycle time of the
Sync telegram/signal.
•
Parameter setting is only
required for the slave!
Synchronisation via system bus (C1120 = 1)
Synchronisation via terminal (C1120 = 2)
•
The master sends a periodic Sync telegram for synchronisation.
Sync telegram.
•
The value set under C1121 is the time between two Sync
telegrams of the master.
Sync telegrams of the master.
•
The master sends a periodic Sync telegram for synchronisation.
Sync signal.
•
The value set under C1121 is the time between two
Sync signals (LOW-HIGH edge) of the master on the corresponding
terminal.
Phase shift
Code
LCD
Possible settings
IMPORTANT
Lenze Choice
[C1122] Sync phase
0
0
{0.001 ms}
6.5
Synchronisation phase
Phase shift between the Sync tele-
gram/signal and the start of the in-
ternal control program.
Synchronisation monitoring (time window)
The variable
CAN_bSyncInsideWindow_b can be used for synchronisation monitoring.
Code
LCD
Possible settings
IMPORTANT
Lenze Choice
[C1123] Sync window
0
0
{0.001 ms}
6.5
Synchronisation window
If the Sync telegram/signal from the
master is within this ”time window”,
CAN_bSyncInsideWindow_b = swit-
ches to TRUE.
Sync signal
Sync window
SyncCycle
SyncCycle
Fig. 6-11
”Time window” for the LOW-HIGH edges of the Sync signal