DeviceNet
10
Installation
10-5
L
BA2175 EN 2.0
A CAN line can have max. 63 devices. Devices are
•
connected controllers
•
masters
•
all components taking part in the communication
The following diagram shows a network:
By means of this network 8200 vector controllers with attached 2175 fieldbus modules
0
can
communicate with the DeviceNet master.
For easy configuration of the fieldbus modules a PC with “ DeviceNet Manager” software
1
can be
used.
2175DeN010
A
B
Fig. 10-1
DeviceNet line
The assignment of the plug/socket connector is described in chapter 10.3.2.
Chapter 9.5.1.3 informs about maximum cable lengths.
Not shown is the voltage supply required for the fieldbus modules.
Note!
Please take into consideration that
•
the shield of the DeviceNet cable is connected with each side
(plug/socket connector, connection: Shield).
•
a bus termination of 120 Ohm is available on both ends of the network.
•
the shield is connected to GND on the master side.