CANopen
6
Parameter setting
6-44
L
BA2175 EN 2.0
L-C18xx (for 82xx, 8200 vector and 93XX)
Possible settings
Data
Code
Subcode
Index
Lenze
Selection
Data
type
Name
L-C1810
-
22765
d
= 58ED
h
-
-
VS
Software product code
L-C1811
-
22764
d
= 58EC
h
VS
Software date
L-C1850
-
58C5
h
= 22725
d
1
1
[1]
63 FIX32
Node address
L-C1851
-
58C4
h
= 22724
d
0
0 = 500 kbit/s, 1 = 250 kbit/s
2 = 125 kbit/s, 3 = 50 kbit/s
4 = 1000 kbit/s, 5 = 20 kbit/s
6 = 10 kbit/s
FIX32
Baud rate
L-C1852
-
58C3
h
= 22723
d
0
0 = Slave operation
1 = Master operation
FIX32
Master / slave operation
L-C1853
/1 ... /3
58C2
h
= 22722
d
0
0 = Addressing to CANopen
1 = Addressing to L-C1854/L-C2354
2 = Addressing to LENZE system bus
3 = Addressing to CANopen index
14Xx
h
/18XX
h
FIX32
CAN-INx/CAN-OUTx
addressing
L-C1854
/1 ... /2
/3* ... /6*
58C1
h
= 22721
d
/1: 129
/2: 1
/3: 257*
/4: 258*
/5: 385*
/6: 386*
0
[1]
1663 FIX32
CAN-IN/CAN-OUT selective
addressing
L-C1855
/1 ... /2
/3* ... /6*
58C0
h
= 22720
d
0
0
[1]
2047 FIX32
Resulting identifier display
L-C1856
/1 ... /5
58BF
h
= 22719
d
/1:
3000 ms
/2 .. /5:
0 ms
0
[1 ms]
65535 FIX32
Boot-up and cycle times
L-C1857
/1 ... /4
58BE
h
= 22718
d
3000 ms 0
[1 ms]
65535 FIX32
Monitoring time
L-C1859
-
58BC
h
= 22716
d
-
0
[1]
1023 U16
DIP-switch position display
L-C1860
-
58BB
h
= 22715
d
-
0
[1]
1023 U16
Current DIP switch position
display
L-C1867
-
58B4
h
= 22708
d
128
0
[1]
2047 FIX32
Sync Rx identifier
L-C1868
-
58B3
h
= 22707
d
128
0
[1]
2047 FIX32
Sync Tx identifier
L-C1873
/1
/2*, /3*
58AE
h
= 22702
d
1
1
[1]
240 FIX32
CAN-IN1 ... CAN-IN3 sync
rate
L-C1874
/1
/2*, /3*
58AD
h
= 22701
d
1
0
[1]
240 FIX32
CAN-OUT1 ... CAN-OUT3
sync rate
L-C1875
/1
/2*, /3*
58AC
h
= 22700
d
/1: 0
/2: 1*
/3: 1*
0
[1]
3 FIX32
CAN-OUT1 ... CAN-OUT3
Tx mode
L-C1876
/1 ... /4
58AB
h
= 22699
d
65535
0
[1]
65535 FIX32
CAN-OUT1 HMIs
L-C1877
/1 ... /4
58AA
h
= 22698
d
65535
0
[1]
65535 FIX32
CAN-OUT2 masks
L-C1878
/1 ... /4
58A9
h
= 22697
d
65535
0
[1]
65535 FIX32
CAN-OUT3 masks
L-C1882
/1 ... /5
58A5
h
= 22693
d
0
0
[1]
2
0: No response
1: Controller inhibit
2: Quick stop
FIX32
Monitoring responses
*) not effective when using 82XX, 8200 vector and 93XX controllers
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: [email protected]