CANopen
5
Commissioning
5-1
L
BA2175 EN 2.0
5
Commissioning
Tip!
Settings using GDC or a keypad
Controller address and baud rate can be set using GDC or a keypad. For this, the DIP-switches S1
to S6 must be set to OFF.
Codes L-C0009 (controller address) and L-C0125 (baud rate) are not active if one or several
switches have been set to ON before a restart.
Please see the descriptions for
•
Node address L-C1850/2350
(
^
6-46)
•
Baud rate L-C1851/2351
(
^
6-47)
.
The DIP switch on the front of the 2175 fieldbus module can be used for the following settings:
•
Controller address S1 - S6
•
Baud rate S7 - S9
•
Communication profile S10
Tip!
In default setting all switches are OFF.
The controller address and baud rate set using DIP switches will only be active after a restart.
Only the combinations shown in the following tables are defined:
5.1
Communication profile setting
OPEN
1 2 3 4 5 6 7 8 9 10
ON
OFF
Communication profile
S10
DeviceNet
OFF
CANopen
ON