DeviceNet
11
Commissioning
11-2
L
BA2175 EN 2.0
11.2
Controller address setting
Note!
Please ensure that the addresses are not the same when using several controllers.
1 2 3 4 5 6 7 8 9 10
OPEN
ON
OFF
Address
dec
=
S
6
⋅
2
0
+
S
5
⋅
2
1
+
S
4
⋅
2
2
+
S
3
⋅
2
3
+
S
2
⋅
2
4
+
S
1
⋅
2
5
The address calculation (decimal number) is based on the positions of switches S1 ... S6 (’0’ = OFF
and ’1’ = ON). The numbers must be entered into the equation above.
The equation also indicates the valency of a switch. The sum of valencies results in the controller
addresses to be set (see examples 1 and 2):
Switch valencies:
Switch
S1
S2
S3
S4
S5
S6
Valency
32
16
8
4
2
1
Example:
Switch
S1
S2
S3
S4
S5
S6
Switch position
ON
ON
ON
OFF
OFF
OFF
Address
(= 56
)
32
16
8
0
0
0
11.3
Baud rate setting
Note!
Please ensure that the baud rate is the same for all controllers and the host.
1 2 3 4 5 6 7 8 9 10
OPEN
ON
OFF
Baud rate [kbit/s]
S7
S8
S9
125
OFF
OFF
OFF
250
OFF
OFF
ON
500
OFF
ON
OFF