DeviceNet
12
Parameter setting
12-4
L
BA2175 EN 2.0
Vendor-specific class (class 100) (GET/ SET)
Byte
Instance 1
Byte
•
Attribute 1: Parameter data
Request
Response
1
Code Low
Code Low
2
Code High
Code High
3
Subcode
Subcode
4
Reserve
Status
•
Byte value = 0: No errors
•
Byte value
≠
0: Incorrect message
The byte value indicates the error number. Its meaning is explained in the table below.
5
Data_1 Low
Data_1 Low
5
..
Data_1 High
Data_1 High
..
..
Data_2 Low
Data_2 Low
Data_2 High
Data_2 High
.
.
.
.
.
.
.
.
Data_22 Low
Data_22 Low
Data_22 High
Data_22 High
The following table lists the explanations for the error numbers:
Error code
(hex)
Explanation
03
Invalid data type
04
Invalid subcode no.
05
Invalid code no.
07
No access during operation
08
No access because of operating mode
09
No access because parameters can only be read
0A
No access authorisation
0B
Data block too long
0C
Collision with other value ranges
0D
Quit value range
0E
General value range error
2X
Error in AIF interface
jFF
General error
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: [email protected]