IOM / Rooftop Smart and Linéa™ Range - Page 73
Min.
Factory
Maxi.
55
Differential temperature, heating setting between 2 steps
0.1
1.0
10.0
56
Differential temperature, engaged cooling setting
0.0
1.0
10.0
57
Differential temperature, cold setting between 2 steps
0.1
1.0
10.0
58
(Not used - special option only)
On = Compressors then chilled water coil, room setting
Off
Off
On
59
On = Heat pump and/or sas then hot water coil or elec. heat, room setting
Off
On
On
60
On = Gas then heat pump, room setting
Off
Off
On
61
On = Supply setting on
Off
Off
On
62
Time, sampling of supply setting (integration delay)
1
10
120
63
On = Compressors then chilled water coil, supply setting
Off
Off
On
64
On = Heat pump and/or gas then hot water coil or elec. heat, supply setting
Off
Off
On
65
On = Gas then heat pump, supply setting
Off
Off
On
66
(Not used - Future facility) - Reserved
On = constant supply air temperature via air damper modulation
Off
Off
On
67
(FLEXY™ only)*
Time, Sampling of humidity setting
1
10
120
68
(FLEXY™ only)*
Humidity range (%), humidity setting
1
5
50
69
(FLEXY™ only)*
Differential humidity (%), Engaged dehumidity setting
1
5
50
70
(FLEXY™ only)*
Differential humidity (%), Dehumidity setting between 2 steps
1
5
50
71
Supply temperature, low setpoint, 1st level
setpoint
72
+2.0
8.0
19.0
72
Supply temperature, low setpoint, 2nd level
setpoint 73
+2.0
6.0
17.0
73
Supply temperature, low setpoint, 3rd level
1.0
2.0
15.0
74
Supply temperature, high setpoint, 1st level
20.0
40.0
70.0
75
Supply temperature, high setpoint, 2nd level
setpoint
74
60.0
70.0
76
Temperature, Outside air minimum setpoint,
(Outdoor air <Setpoint 76 = No free cooling, Min % fresh air)
0.0
5.0
30.0
77
Temperature, Outside air maximum setpoint,
(Outdoor air>Setpoint 77 = 50 % compressors OFF in cooling)
0.0
26.0
60.0
78
(Not used - future facility) - Percentage, maximum fresh air,
Damper modulation to provide constant supply air temperature
0
60
100
79
Outside air temperature, setpoint, 50% compressor
(Outdoor air<Setpoint 79 = 50 % compressors stop)
10.0
12.0
30.0
80
Outside air temperature, setpoint, 100% compressor
(Outdoor air<Setpoint 80 = ALL compressors stop)
10.0
12.0
30.0
81
Icing temperature setpoint, evaporator coil
-5.0
-1.0
3.0
82
Defrost temperature setpoint, evaporator coil
5.0
10.0
15.0
83
Delay, icing setpoint, evaporator coil
1
360
600
84
Outside air temperature, setpoint, 100% compressor heatpump
(Outdoor air<Setpoint 84 = ALL compressor stop)
-50.0
-20.0
20.0
85
Outside temperature, setpoint, authorised defrosting, condenser coil
8.0
10.0
20.0
86
(on LINEA™ only) - (R22 = -3, R407C = 1)
Battery temperature, setpoint, authorised defrosting, condenser coil
-10.0
-3.0
6.0