Page 74 - IOM / Rooftop Smart and Linéa™ Range
Min.
Factory
Maxi.
87
Coefficient, icing time, condenser coil
0
3
12
88
Number, condenser restart, condenser coil
1
1
8
89
Low temperature, setpoint,
air/water cooled heat exchanger (non standard)
4.0
5.0
20.0
90
High temperature, setpoint,
air/water cooled heat exchanger (non standard)
20.0
45.0
46.0
91
Outside temperature, setpoint, 100% electrical heater discharge
(Outdoor air > Setpoint 91 = electric heater stop)
-20.0
10.0
30.0
92
Sensing setpoint, air flow cutout
0.0
0.2
5.0
93
Sensing setpoint, clogged filters
0.0
2.5
5.0
94
Sensing setpoint, missing filters
0.0
0.5
5.0
95
KP17 = on = On/Off unit
Off
Off
On
96
Delay, closing, KP 12-2 "Day" input
4
60
65535
97
Delay, Opening, KP 12-2 "Day" input
2
300
65535
98
Unit type
0
0
65535
99
On = "LINEA™" series, Off = "FLEXY™" series*
Off
#
On
100
On = Low ambiant Option fitted
(Disable setpoints 79&80) (Off = Enable setpoints 79 & 80)
Off
#
On
101
(FLEXY™ only)*
On = Advanced Control Pack option fitted
Off
#
On
102
Slave J-Bus, number
1
1
10
103
Link, number
0
0
7
104
All setpoint values overide to factory
default EPROM values (centre column)
Off
Off
On
105
Test stages (for factory test procedures only
reduces all delay timers to 0)
0
0
65535
* : FLEXY™ is an other range of ROOFTOP. For more informations, please consult your regional office
USING THE KP02 MAINTENANCE CONTROL DISPLA