THERMOSTAT INSTALLER SETUP OPTIONS (continued)
Setting Keypad Lockout Switch
The DIP switch 1, on the back of the thermostat, activates
the lockout features. The switch must be set to the ON
position (up) to activate the lockout feature. See figure 73.
The factory setting is off (down). Remove the thermostat
from the subbase and set the switch to ON if keypad lockout
is desired.
The level of lockout is determined by the Installer Setup
numbers 25 and 40.
ON
1
2
1
2
1
2
Figure 73
SET THE KEYPAD LOCKOUT DIP SWITCH 1
ON BACK OF THERMOSTAT
DIP 1 is ON
DIP 2 is NOT USED
Factory setting
Other choices
(press
▲
or
▼
key to change)
Actual
setting
Select
Installer setup
number (press
unocuppied
temp. key to
change
Display
Description
Display
Description
Temperature
range stops in
cooling (T7300)
35
45
Lowest cooling setpoint
46 to 89
Temperature range (0.6°C
increments) for cooling setpoint
Not used
36
-
-
-
-
-
Temperature
display
adjustment
37
0
No difference in displayed
temperature and actual
room temperature
1 thru 6
1-Display adjusts to 0.6°C
higher than actual room
temperature.
2-Display adjusts to 1.1°C
higher than actual room
temperature.
3-Display adjusts to 1.7°C
higher than actual room
temperature.
4-Display adjusts to 0.6°C lower
than actual room
temperature.
5-Display adjusts to 1.1°C lower
than actual room
temperature.
6-Display adjusts to 1.7°C lower
than actual room
temperature.
Minimum off-
times in heating
38
4
4 – 4 minute minimum
off-time
0, 1, 2, 3
or 5
Minimum number of minutes (0
thru 5) the heating equipment is
off between calls for heat
Not used
39
-
-
-
-
-
Installer Setup
lockout (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat).
40
0
0 - Installer Setup
lockout.
1
1 - Installer Setup lockout
activated.