IOM / Rooftop Smart and Linéa™ Range - Page 75
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLAY
Y
Y
Y
Y
VARIABLE LIST
(june 2001)
1st Level
0
Error code
1
Temperature, room
2
Relative humidity (%),room
3
Temperature, outside air
4
Relative humidity (%), outside, air
5
Temperature, supply Air
6
Temperature, chilled water battery
7
Temperature, compressor, no. 1
8
Temperature, compressor, no. 2
9
Temperature, compressor, no. 3
10
Temperature, compressor, no. 4
11
Temperature, condenser, no. 1
12
Temperature, condenser, no. 2
13
Temperature, condenser, no. 3
14
Temperature, condenser, no. 4
15
Temperature, air/water cooled heat exchanger, water outlet
16
Pressure, air flow (mb)
17
Air quality sensor, CO² (ppm)
18
Pressure, compressor, no. 1
19
Pressure, compressor, no. 2
20
Pressure, compressor, no. 3
21
Pressure, compressor, no. 4
22
Volt free contact, remote control, unit Off
23
Volt free contact, remote control, forced occupied mode
24
Volt free contact, remote control, forced unoccupied mode
25
Volt free contact, remote control, 50% load limit
26
Volt free contact, remote control, heating disable
27
Volt free contact, remote control, cooling disable
28
Volt free contact, remote control,low ventilation speed
29
Auxiliary contact, blower fan
30
Volt free contact, error, DAD board, detected smoke
31
Auxiliary contact, compressor, no. 1
32
Auxiliary contact, compressor, no. 2
33
Auxiliary contact, compressor, no. 3
34
Auxiliary contact, compressor, no. 4
35
Pressure switch, compressor, no. 1, low pressure
36
Pressure switch, compressor, no. 2, low pressure
37
Pressure switch, compressor, no. 3, low pressure
38
Pressure switch, compressor, no. 4, low pressure
39
Auxiliary contact, condenser fan, no. 1
40
Auxiliary contact, condenser fan, no. 2
41
Auxiliary contact, condenser fan, no. 3
42
Auxiliary contact, condenser fan, no. 4
43
Volt free contact, air/water cooled heat exchanger, water flow regulator
44
Auxiliary contact, pump (hot water coil - frost protection pump)
45
Auxiliary contact, electrical heater, no. 1
46
Auxiliary contact, electrical heater, no. 2
47
Auxiliary contact, gas grade, no. 1
48
Auxiliary contact, gas grade, no. 2
49
Volt free contact, humidifier, error, control & setting board
50
Volt free contact, leak water
51
Volt free contact, information, miscellaneous source
52
Output, supply fan
53
Output, low speed supply fan