IOM / Rooftop Smart and Linéa™ Range - Page 71
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLAY
Y
Y
Y
Y
LIST OF SETPOINTS
1st Level
Min.
Factory
Maxi.
0
Password to access level 2 setpoints and variables
0
#
255
1
Temperature, required setpoint for room, day mode
8.0
21.0
35.0
2
(Used by KP17 only)
KP17 Remote control, overide, occupied mode
Off
Off
On
3
(Used by KP17 only)
KP17 Remote control, overide, automatic mode
Off
Off
On
4
(Used by KP17 only)
KP17 Remote control, overide, unoccupied mode
Off
Off
On
5
Fault reset
Off
Off
On
6
Remote control, On / Off, unit
Off
Off
On
7
(Special software request)
Remote control, On / Off, customer output KP12/2
Off
Off
On
8
(Used for setting up different time zones)
0
0
7
Mode, Selection
0 = Day
1 = Week-end
2 = Night
3 =
4 = Morning
5 = Midday
6 = Evening
7 = BMS
9
Defines end of weekend/Start of week (1 = Sunday, 2 = Monday, etc)
1
#
7
Mode, day of the weekn start of mode
10
(Used with setpoint 8 - mode selection - to define the hour of the start time)
0
#
23
Mode, hour, start of mode
11
Used with setpoint 8 - mode selection - to define the minute of the start time
0
#
59
Mode, minute, start of mode
12
Defines end of week/Start of weekend (6 = Friday, 7 = Saturday, etc)
1
#
7
Mode,day of the week, end of mode
13
Used with setpoint 8 - mode selection - to define the hour of the stop time
0
#
23
Mode, hour, end of mode
14
Used with setpoint 8 - mode selection - to define the minute of the stop time
0
#
59
Mode, minute, end of mode
15
Defines day mode deadzone, other time zones = cooling setpoint)
8.0
#
35.0
Mode, temperture, room cooling setpoint
16
Defines day mode deadzone (other time zones = heating setpoint)
8.0
#
35.0
Mode, temperature, room heating setpoint
17
(FLEXY™ only)*
On = Absolute humidity (g/kg) / Off = Relative humidity (%)
Off
Off
On
18
(FLEXY™ only)*
Mode, relative humidity (%), room minimum setpoint required
0
#
100
19
(FLEXY™ only)*
Room mode, Relative humidity (%), maximum setpoint required
0
#
100
20
(FLEXY™ only)*
Mode, Absolute humidity (g/kg), room minimum setpoint required
0.0
#
30.0
21
(FLEXY™ only)*
Mode, Absolute humidity (g/kg), room maximum setpoint required
0.0
#
30.0
22
Mode, Percentage, Minimum fresh air
0
#
100
23
Mode, Fan activity in control zone (cooling mode/heating mode)
Off
#
On
24
Mode, Fan activity in dead zone
Off
#
On
25
(Special application request only)
Mode, Fan automation, dead zone
Off
#
On
26
(FLEXY™ only)*
Mode, Fan low speed, control zone
Off
#
On
* : FLEXY™ is an other range of ROOFTOP. For more informations, please consult your regional office