IOM / Rooftop Smart and Linéa™ Range - Page 55
USING THE T7300 THERMOS
USING THE T7300 THERMOS
USING THE T7300 THERMOS
USING THE T7300 THERMOS
USING THE T7300 THERMOST
T
T
T
TA
A
A
A
AT
T
T
T
T
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow the
instructions can damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions to
check out the product operation.
Location
Q7300 Subbase without Remote-Mounted
Temperature Sensor
Install the thermostat about 1.5 meters above the floor in an
area with good air circulation at average temperature. See
figure 66.
Do not install the thermostat where it can be affected by :
- drafts, or dead spots behind doors and in corners,
- hot or cold air from ducts,
- radiant heat from sun or appliances,
- concealed pipes and chimneys,
- unheated (uncooled) areas such as an outside wall
behind the thermostat.
Figure 66
TYPICAL LOCATION OF THERMOSTAT OR REMOTE-MOUNTED SENSOR
NO
NO
NO
YES
1,5 m
Q7300 Subbase with Remote-Mounted
Temperature Sensor(s)
If only the remote-mounted temperature sensor(s) is used
to sense and control room temperature, then install the
thermostat in an area that is accessible for setting and
adjusting the temperature and settings.
If both the subbase and remote-mounted temperature
sensor(s) are used to sense and control room temperature,
then install the subbase about 1.5 meters above the floor in
an area with good air circulation.
Install the remote-mounted sensor(s) about 1.5 meters
above the floor in an area with good air circulation at average
temperature. See figure 66.
Do not mount the sensor(s) where it can be affected by :
- drafts, or dead spots behind doors and in corners,
- hot or cold air from ducts,
- radiant heat from sun or appliances,
- concealed pipes and chimneys,
- unheated (uncooled) areas such as an outside wall
behind the thermostat.
If more than one remote sensor are required, they must be
arranged in a temperature averaging network consisting of
two, three, four, five or nine sensors.