Page 72 - IOM / Rooftop Smart and Linéa™ Range
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLAY
Y
Y
Y
Y
Min.
Factory
Maxi.
27
(FLEXY™ only)*
Mode, Fan low speed, dead zone
Off
#
On
28
(FLEXY™ only)*
Mode, Fan low speed automation
Off
#
On
29
(on = Unit runs at maximum 50% during "night mode")
Mode, Low noise
Off
#
On
30
(J-BUS only)
Remote control, overide, Mode
Off
Off
On
31
(J-BUS only)
Remote control, Overide, Low fan speed
Off
Off
On
32
(J-BUS only)
Remote control, Overide damper with recycled air
Off
Off
On
33
(J-BUS only)
Remote control, Overide damper with minimum fresh air
Off
Off
On
34
(J-BUS only)
Remote control, Overide damper with fresh air
Off
Off
On
35
(J-BUS only)
Remote control, Overide 50% load limit
Off
Off
On
36
(J-BUS only)
Remote control, Overide heating cancellation
Off
Off
On
37
(J-BUS only)
Remote control, Overide cooling cancellation
Off
Off
On
38
(J-BUS only)
Remote control, Overide electrical heaters cancellation
Off
Off
On
39
On = Electrical heaters during defrosting
Off
On
On
40
(Alarm only)
Room temperature, low setpoint
5.0
10.0
20.0
41
(Alarm only)
Room temperature, high setpoint
20.0
40.0
40.0
42
Room relative humidity (%), low setpoint
0
0
50
43
Room relative humidity (%), high setpoint
50
100
100
44
Room absolute humidity (g/kg), low setpoint
0.0
0.0
30.0
45
Room absolute humidity (g/kg), high setpoint
0.0
30.0
30.0
46
Temperature, Curved gradient of anticipated speed
0.0
10.0
20.0
47
(0 = Start at times set in "modes" only, no anticipation start
0
12
100
Value, Gradient of anticipated speed
48
Quantity of CO2, Ppm, minimum fresh air
0
1000
2000
49
Quantity of CO2, Ppm, maximum fresh air
0
1500
2000
50
Percentage, Fresh air damper opening before fan will start
0
10
100
2nd Level
Min.
Factory
Maxi.
51
Maximum temperature, required setpoint for room, day mode
21.0
27.0
35.0
52
Minimum temperature, required setpoint for room, day mode
8.0
17.0
21.0
53
(Compressor minimum run time in seconds)
25
180
1800
54
Differential temperature, engaged heat setting
0.0
1.0
10.0
* : FLEXY™ is an other range of ROOFTOP. For more informations, please consult your regional office