Page 46
TABLE 35
580682
LGH/LCH092H4M, 102H4M, 120H4M, 150H4M (2-Compressor) Staged Belt Drive
Para
meter
Factory Setting
Field
Setting
Description
092
102
120
150
Note: Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT
PARAMETERS
12
3000
CFM
3400
CFM
4000
CFM
5000
CFM
CFM
Blower CFM during smoke detection.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > BLOWER > SPEEDS)
3000
CFM
3400
CFM
4000
CFM
5000
CFM
CFM
Blower CFM during heating.
2700
CFM
2200
CFM
3600
CFM
4500
CFM
CFM
Blower CFM during high speed (2 compressor) cooling.
1950
CFM
3050
CFM
2600
CFM
3250
CFM
CFM
Blower CFM during low speed (1 compressor) cooling.
3000
CFM
3400
CFM
4000
CFM
5000
CFM
CFM
Blower CFM during ventilation.
*Once all four blower settings are entered, the target (highest of the heating and cooling settings) CFM will be displayed. Once the target CFM is
saved, all other blower CFM are set by the Unit Controller.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > DAMPER)
0%
0%
0%
0%
%
Damper min. position during LOW blower operation.
0%
0%
0%
0%
%
Damper min. position during HIGH blower operation.
50%
50%
50%
50%
%
Min. damper % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETERS
29
101%
101%
101%
101%
%
Open
Damper minimum position during G blower operation. (Setting parameter 29 to “101”
disables parameter 29 and passes control to parameter 9 or 132)
216
5%
5%
5%
5%
%
Deadband % for stage 1 power exhaust operation.
TABLE 36
580686
LGH/LCH094U4M, 122U4M, 152U4M (2-Compressor) Staged Belt Drive
Paramet
er
Factory Setting
Field
Setting
Description
094
122
152
Note: Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT
PARAMETERS
12
3000 CFM
4000 CFM
5000 CFM
CFM
Blower CFM during smoke detection.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > BLOWER > SPEEDS)
3000 CFM
4000 CFM
5000 CFM
CFM
Blower CFM during heating.
2700 CFM
3600 CFM
4500 CFM
CFM
Blower CFM during high speed (2 compressor) cooling.
1950 CFM
2600 CFM
3250 CFM
CFM
Blower CFM during low speed (1 compressor) cooling.
3000 CFM
4000 CFM
5000 CFM
CFM
Blower CFM during ventilation.
*Once all four blower settings are entered, the target (highest of the heating and cooling settings) CFM will be displayed. Once the target CFM is
saved, all other blower CFM are set by the Unit Controller.
SETUP > TEST & BALANCE (can also use SETTINGS > RTU OPTIONS > DAMPER)
0%
0%
0%
%
Damper min. position during LOW blower operation.
0%
0%
0%
%
Damper min. position during HIGH blower operation.
50%
50%
50%
%
Min. damper % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETERS
29
101%
101%
101%
%
Open
Damper minimum position during G blower operation. (Setting paramet
er 29 to “101” disables parameter 29 and passes control to parameter 9
or 132)
216
5%
5%
5%
%
Deadband % for stage 1 power exhaust operation.
SETTINGS > RTU OPTIONS > EDIT PARAMETER
85
40°F
40°F
40°F
°F
Compressor 1 low temp lockout. Settings lower than 40°F could void
warranty.
86
40°F
40°F
40°F
°F
Compressor 2 low temp lockout. Settings lower than 40°F could void
warranty.