9.4.3 Battery Drawers
There are two different procedures for installing/replacing battery drawers inside UPS Trimod® and UPS BATTERY Trimod®.
Carefully read all instructions before operating on the equipment.
The drawers batteries must always be added/replaced in multiples of 4 (1 KB).
Note
: if the installation/replacement has changed the total number of KB installed in the UPS, you must update the
number of KB via the front panel.
After completing the procedure above described, we recommand to calibrate batteries in order to get correct informations
about UPS runtime.
If the UPS has more than 1 KB for each 10kVA output power, you can replace 1 KB at a time with UPS Online.
This operation can be done inside UPS Trimod® and/or UPS BATTERY Trimod®.
Remember that 1 KB consists of 4 battery drawers.
The replacement procedure is as follows:
1. Make sure the UPS has installed at least every 1KB 10kVA output power output plus one;
2. Make sure the UPS is not operating on battery and the charger is maintenance or standby state. To check the status of
the charger, enter the state ups -> Measures -> batteries, and check the fourth item shown on the display.
3. Remove the four battery drawers (n° 1KB).
4. Insert the new 4 batteries drawers and secure them with the screws provided;
5. Repeat steps 2, 3 and 4 for each KB to install/replace.
In the case of simple addition of KB is enough to follow the steps 2, 4 and 5.
WARNING
Always replace only 1 KB at a time
Note
: If the UPS switches to battery while you are performing the operation, stop and do not remove or insert battery
drawers! it is possible to resume operation when the UPS returns to work on-line.
Note
: if during the operation mains is missing, you will have a reduced autonomy: you should therefore carefully consider
such cases in relation to the application before starting.
Installation / replacement battery drawers in UPS maintenance bypass
This procedure applies to each model of UPS Trimod® and UPS BATTERY Trimod®.
WARNING
In maintenance bypass the load is powered directly from the mains input.
1. To bring the UPS in maintenance bypass mode follow steps 1 to 8 described in paragraph 9.3.1.
2. Remove the four battery drawers (n° 1KB).
To add another KB (if there is enough space available) does not remove any battery drawer;
3. Insert the new four batteries drawers and secure with the screws provided;
4. Repeat steps 2 and 3 for each KB to install / replace.
5. Follow steps 1 to 6 described in section 9.4.2 to bring state of the UPS maintenance bypass switch to the On-line.
In the case of simple addition of KB is sufficient to perform the steps described in paragraphs 1, 3, 4 and 5.
9. Maintenance
Содержание Trimod 10 kVA
Страница 1: ...Trimod Operating and Maintenance Manual Part LE05768AA 07 12 01 GF ...
Страница 2: ... 2 EN ENGLISH 3 Trimod ...
Страница 12: ...12 UPS Trimod 10 UPS Trimod 10 15 20 2 3 Models 2 Technological description ...
Страница 13: ...Trimod Operating and Maintenance Manual 13 UPS Trimod 10 15 20 UPS Trimod 30 TT ...
Страница 14: ...14 UPS Trimod 30 TM UPS Trimod 40 2 Technological description ...
Страница 15: ...Trimod Operating and Maintenance Manual 15 UPS Trimod 60 ...
Страница 16: ...16 2 Technological description UPS Trimod BATTERY UPS Trimod BATTERY 2 ...
Страница 42: ...42 5 Installation UPS Trimod 30TM ...
Страница 43: ...Trimod Operating and Maintenance Manual 43 UPS Trimod 30TT ...
Страница 44: ...44 UPS Trimod 40 60 5 Installation ...
Страница 46: ...46 5 Installation ...