(*) Available in the “Service Mode” only
ATTENTION
Set the total KB value and Capacity correctly for the batteries being used. If set incorrectly there is the danger of
damaging the batteries.
Bypass
Bypass Enabling
If enabled, the UPS controls triggering of the bypass automatically.
If disabled, the UPS will never switch over to bypass and, therefore,
in the case of a prolonged overload (see “Overloaded permitted”
in Chap. Technical Description), or In the case of a failure and
redundancy absence, the UPS switches off.
Forced Mode
If enabled, the UPS activates the bypass permanently.
In this case the load is not protected.
DIP speed
It allows variation of the automatic bypass activation sensitivity
(forced mode disabled)
- SLOW: loads that are not sensitive to drops in voltage or
microinterruptions but which provoke frequent current peaks.
- STANDARD: normal uses.
- FAST: loads sensitive to the microinterruptions
Start with Bypass
If enabled, when the mains are switched on, the first load feeding
by the UPS is via the bypass. If disabled, the load peak will be handled
by the inverter, as happens when switching on with the battery.
Batteries
Threshold
Values
Aut end warning
Setting the start time of the end
of battery autonomy warning
Max. Battery time
Setting the maximum time of the UPS
running on battery [sec].
When this battery time is up the UPS
shuts down.
Set OFF to disable to function
Battery Charger
Charge in Standby
If enabled, it enables battery charging
with the UPS off
Restart
Restart Enabling
Enables or disables restarting of the unit
when mains power returns after the
batteries have run down completely
Minimum autonomy
Minimum percentage of autonomy
to preserve
Total KBs
Sets the total number of KBs installed (1 KB = 4 battery boxes)
Necessary for the UPS to supply correct autonomy values on the
basis of the load applied and for correct battery charging.
Capacity (*)
Sets the capacity value of the batteries in the UPS [Ah]
Содержание Trimod 10 kVA
Страница 1: ...Trimod Operating and Maintenance Manual Part LE05768AA 07 12 01 GF ...
Страница 2: ... 2 EN ENGLISH 3 Trimod ...
Страница 12: ...12 UPS Trimod 10 UPS Trimod 10 15 20 2 3 Models 2 Technological description ...
Страница 13: ...Trimod Operating and Maintenance Manual 13 UPS Trimod 10 15 20 UPS Trimod 30 TT ...
Страница 14: ...14 UPS Trimod 30 TM UPS Trimod 40 2 Technological description ...
Страница 15: ...Trimod Operating and Maintenance Manual 15 UPS Trimod 60 ...
Страница 16: ...16 2 Technological description UPS Trimod BATTERY UPS Trimod BATTERY 2 ...
Страница 42: ...42 5 Installation UPS Trimod 30TM ...
Страница 43: ...Trimod Operating and Maintenance Manual 43 UPS Trimod 30TT ...
Страница 44: ...44 UPS Trimod 40 60 5 Installation ...
Страница 46: ...46 5 Installation ...