MESSAGE
MEANING
First start-up: connectthe mains!
The UPS has never been switched on. No mains supply. Start-up not allowed.
Make sure the mains are present before starting up.
No mains! start-up not allowed
No mains supply. Start-up not allowed.
To start the UPS on battery, select this con
fi
guration via the display.
Emergency Power Off!
The Emergency Power O
ff
(EPO) is working, the EPO command has been given
by a push button or a disconnecting switch on the input line was opened while
the UPS was working.
Config. incomplete for start-up!
The UPS requires a complete start-up con
fi
guration.
Ensure that the output con
fi
guration, bypass enable, KB number, number
of batteries for KB and the output voltage have been entered correctly.
Three-phase circuit sequence
incorrect!
Invalid three-phase input sequence. Check that the three-phase circuit has
been connected correctly.
The pms’ hw versions are incorrect
One or more Power Modules are not compatible with the UPS.
Call assistance.
Start-up error!
An error occurred during start-up of the UPS.
Start-up interrupted
Start-up possible only by con
fi
rming.
Start-up was not con
fi
rmed within 30 seconds.
UPS shut down by programming!
UPS shut down by programming.
Shutting down due to an incorrect
configuration
An error occurred in con
fi
guration. UPS in shutting down.
The number of Power Modules detected by the UPS is incorrect for the output
con
fi
guration set.
Shutting down due to a wrong
KBnumber “
An error occurred when con
fi
guring the KBs.
Set the right KB number.
Shutting down due
to end of autonomy
Battery charge level is too low, UPS in shutting down.
Maximum time on battery
The UPS has been running on battery for the maximum time set,
UPS shutting down.
Load not fed.
Load feeding interrupted.
Feeding from the output
Error in starting up. Voltage present on the UPS output.
Check connections.
Shutting down with H.V.
buses loaded
The UPS did not shutdown correctly. Make sure the DC buses are discharged
prior to carrying out any maintenance on the unit.
Current data saving error
Error in saving some of the UPS parameters.
FRAMES DISPLAYED WHEN SHUTTING DOWN
Содержание Trimod 10 kVA
Страница 1: ...Trimod Operating and Maintenance Manual Part LE05768AA 07 12 01 GF ...
Страница 2: ... 2 EN ENGLISH 3 Trimod ...
Страница 12: ...12 UPS Trimod 10 UPS Trimod 10 15 20 2 3 Models 2 Technological description ...
Страница 13: ...Trimod Operating and Maintenance Manual 13 UPS Trimod 10 15 20 UPS Trimod 30 TT ...
Страница 14: ...14 UPS Trimod 30 TM UPS Trimod 40 2 Technological description ...
Страница 15: ...Trimod Operating and Maintenance Manual 15 UPS Trimod 60 ...
Страница 16: ...16 2 Technological description UPS Trimod BATTERY UPS Trimod BATTERY 2 ...
Страница 42: ...42 5 Installation UPS Trimod 30TM ...
Страница 43: ...Trimod Operating and Maintenance Manual 43 UPS Trimod 30TT ...
Страница 44: ...44 UPS Trimod 40 60 5 Installation ...
Страница 46: ...46 5 Installation ...