3.6 VENTING TO AN EXISTING MASONRY FIREPLACE CHIMNEY
In some situations, a code compliant chimney originally used for a masonry fireplace
may be used to install your Super Magnum Coal Stoker stove. In addition to the
requirements found in the previous paragraphs, it is important to be aware that all
clearances must be met, including those from the chimney connector to combustibles —
18" (360 mm) to sides and 18" (450 mm) to ceiling. Do not forget to include floor
protection in your plans. (See Clearances and Floor Protection in a previous section.)
Since many fireplaces have exposed wooden mantels and trim, pay special attention to
the clearances necessary to these materials.
If your fireplace chimney is behind a combustible wall, you must use an approved wall
pass-through system to gain access to the masonry chimney. The chimney connector
must enter the chimney at a place where it is lined, and the fireplace must be made
inoperable. For example, you might remove the damper, replacing it with a secure,
airtight, noncombustible seal (removable for inspection); this also satisfies the
requirement that no room air must be allowed to enter the chimney.
-19-
DO NOT BURN ANY FUEL OTHER THAN COAL. NEVER
USE HIGHLY VOLATILE SUBSTANCES IN YOUR STOVE,
SUCH AS GASOLINE, WHICH COULD CAUSE AN
EXPLOSION.
Содержание Super Magnum Coal Stoker
Страница 2: ......
Страница 4: ...Super Magnum Coal Stoker Label top not actual size 4 ...
Страница 5: ...Super Magnum Coal Stoker Label bottom not actual size 5 ...
Страница 6: ... 6 ...
Страница 12: ...2 4 COMPONENT LOCATIONS 12 ...
Страница 14: ...2 6 DIMENSIONS 14 ...
Страница 37: ...Reference Materials 37 ...
Страница 45: ...Service and Maintenance Log Date of Service Performed By Description of Service 45 ...
Страница 46: ...Service and Maintenance Log Date of Service Performed By Description of Service 46 ...