2.7 CLEARANCES
2.8 FLOOR PROTECTION REQUIREMENTS
Floor protection must be of a non-combustible material. It must be located
under the appliance and extend beyond the appliance according to the
measurements below. Floor protection must also extend under any horizontal
sections of chimney connector and 2" (50.8mm) beyond each side of the
connector.
DANGER: The appliance legs may not be removed for installation.
Minimum Size floor protection is 49½" Deep By 42¾" Wide.
Alternate floor protector dimension may be used as long as they satisfy the
measurement requirements shown above.
Minimum size floor protection for a corner installation hearth pad is 54" x 54"
(USA ONLY).
-15-
Parallel Installation
Inches
Millimeters
A
Back Wall to Unit (Hopper)
2
51
B
Side Wall to unit
24
610
C
Back Wall to Flue Connector
17
432
D
Side Wall to Flue Connector
34
864
Corner Installation
Pouces
Millimeters
E
Walls to Unit Body
15
381
F
Walls to Flue Connector
24
610
Inches
Millimeters
G
Sides – USA/Canada*
8
203
H
Front – USA/Canada*
18
457
J
Rear – USA
12
305
Floor Protection
Requirements
CAUTION! DO NOT STORE FUEL INSIDE INSTALLATION CLEARANCES!
Содержание Super Magnum Coal Stoker
Страница 2: ......
Страница 4: ...Super Magnum Coal Stoker Label top not actual size 4 ...
Страница 5: ...Super Magnum Coal Stoker Label bottom not actual size 5 ...
Страница 6: ... 6 ...
Страница 12: ...2 4 COMPONENT LOCATIONS 12 ...
Страница 14: ...2 6 DIMENSIONS 14 ...
Страница 37: ...Reference Materials 37 ...
Страница 45: ...Service and Maintenance Log Date of Service Performed By Description of Service 45 ...
Страница 46: ...Service and Maintenance Log Date of Service Performed By Description of Service 46 ...