Glossary UH50 – FOR INTERNAL USE ONLY!
Gyr GmbH
Glossary UH606-101b
Page
19
of
38
Monthly memory
Monthly memory contains the history of the events for the last 18 months. The monthly memory
is implemented as a shift register. The current monthly data is transferred on the parameterized
monthly set day
. The data for the oldest previous month are then lost.
The data in the monthly memory are stored without a time stamp. The memory only indicates
whether an error occurred in the month in question or a certain event occurred. No information
is given, for example, about the duration of the error condition.
NEOVAC lock
see
Display lock
In
normal mode
, flowrate measurement and temperature measurement are performed in a
timebase (
measuring interval
) of 4 seconds (parameterizable: 0.5 / 1 / 2 / 4 or 8 seconds) or
30 seconds (parameterizable: 2 / 4 / 8 / 30 / 60 seconds).
If
power saving mode
(“
saving mode
”) has been parameterized – and the calibration seal is set
– the LCD is only activated once every 5 seconds for approx. 0.5 seconds after 15 minutes of
inactivity (no LCD button is pressed and no data traffic). This mode is exited when an LCD
button is pressed and the LCD then permanently displays. After another 15 minutes of inactivity
(no LCD button pressed and no data traffic through the optical interface), the LCD again
switches to “power saving mode”.
Caution: If the service button is pressed in this state, display mode remains!
The following
notes
have been included in the instructions:
Text
CI
I / SI
OI
•
The electronic unit must only be cleaned on the outside. Please use a
soft, damp cloth to do this, which can be dipped in a non-corrosive
cleaning agent.
- - yes
•
Regulations on the use of heat meters must be observed, see EN 1434,
Part 6! In particular, cavitation in the system must be avoided.
yes yes -
•
Heat meters up to DN25 may only be installed with directly immersed
sensors according to German calibration law!
yes yes -
•
Install the unit in such a way that no water can enter the electronic unit
during operation.
yes yes -
•
All information given on the data sheet of the heat meter must be
observed.
yes yes -
•
User seals may only be removed by authorized persons for service
purposes and must be replaced afterwards.
yes yes yes
•
The unit is supplied with Installation and Service Instructions and with
Operating Instructions.
yes - -
•
No later than 30 seconds after installation, the heat meter detects the
plugged modules automatically and is ready for communication or pulse
output.
yes yes -
•
The type of modules plugged can be displayed in the service loop
depending on how the display is parameterized.
yes yes -
•
For fast pulses, the parameters must be set accordingly with the
PappaWin software.
yes yes -
•
Up-to-date versions of all instructions can be found in the Internet at
www.landisgyr.com
yes yes yes