Page 5
Measurement ranges / Output frequencies Tx-Bus
Option
7.
Temperature sensor PT1000
-20 .. +80 °C
-20 .. +80 °C
800 .. 1800 Hz
Resolution
0.1 °C (1 Hz)
Max. measuring error
± 3 °C
Address on the Tx-bus
n + 6 (n = coded address)
Option
8.
Temperature sensor PT1000*
maximum Temperature since the
most recent compressor cycle
-30 .. +200 °C
-30 .. +200 °C
800 .. 2000 Hz
Resolution
0.2 °C (1 Hz)
Max. measuring error
± 5 °C
Address on the Tx-bus
n + 7 (n = coded address)
Option
9.
Pressure sensor*
0 .. 10 bar rel.
0 .. 10 bar rel.
1000 .. 2000 Hz
Resolution
0.01 bar (1 Hz)
Max. measuring error at 25 °C
±2.5 % FS
Max. temperature drift
±0.075 % FS/°C
Temperature range of the medium 0 .. 90 °C
Address on the Tx-bus
n + 8 (n = coded address)
10. Flow module
ACS 5000
Total air flow
0 .. 5000 l/h (standard liter: 20 °C)
0 .. 5000 l/h
1000 .. 2000 Hz
Resolution
5 l/h (1 Hz)
Max. measuring error
± 10 % FS
Max. overpressure
1 bar
Address on the Tx-bus
n + 9 (n = coded address)
optional
Flow module
ACS 10000
Total air flow
0 .. 10000 l/h (standard liter: 20 °C)
0 .. 10000 l/h
1000 .. 2000 Hz
Resolution
10 l/h (1 Hz)
Max. measuring error
± 10 % FS
Max. overpressure
1 bar
Address on the Tx-bus
n + 9 (n = coded address)
*) These measurement values are sent only after the compressor has finished a
complete cycle.