Page 22
Operate an MFR with the ACS
If a LANCIER pressurization system is equipped with a multi function relay
(MFR), this can be operated and set via the ACS.
Read out MFR Values
Menu selection:
Menu D1
>Disp. Device : MFR
Press softkey „select“
Menu D2.2
>MFR – Current Values
Press softkey „select“
Display
D3.4
„MFR - Current Values“ shows up:
- Runtime
: value sec last compressor run-
time in seconds
- Maintenance : value h
remaining time until
next maintenance in
hours
- Operating
: value h
total operating hours
of the equipment
Reset maintenance counter
The maintenance counter of the MFR can be reset via the ACS.
Go to display
D3.4
as described in chapter „Read out MFR Values“.
Press softkeys „Maint.“ and „reset“ at the same time for 5 seconds.
The value „Maintenance“ will be reset to „400 h“.
This reset is irreversible!
MFR – Current Values
Runtime : 93sec
Maintenance: 178h
Operating : 12345h
________________________
Maint. reset
|
back