48
6
Commissioning
6.6.2
Control Strategy
6.6.2.1 With Pre-setting For Firing Rate Changes
O
2
trim by means of a comparison between target and actual values is only performed if no
output change (firing rate change) takes place (’internal firing rate’ static). After a preceding
firing rate change, an target/actual value comparison is performed and an actuation step trig-
gered only after expiry of the set lag time (parameters 898 and 900).
If the O
2
actual value corresponds to its target value, the current correction value, referenced
to the firing rate vale and the firing rate direction, is stored in a table. The updated value is
output at the next firing rate change.
A pre-update is already carried out as from the 2
nd
target/actual value comparison, after a fir-
ing rate change. As soon as the actual value gets close to the target value, the correction value
is updated.
When the firing rate changes, control is terminated immediately after target/actual value com-
parison and the neutral value, or if relevant the correction value obtained (updated) for this
firing rate point,is output
pre-setting!
Control after a target/actual value comparison is only performed again if the firing rate is sta-
tionary and on expiry of the lag time.
In this type of control, the overshoot is automatically deactivated in the VMS. The actuators'
hysteresis is compensated for by the firing rate direction-dependent updating of the correction
value.
Control strategy with pre-setting for firing rate changes
1
Pre-purge/ignition
The correction is switched off; i.e. the neutral correction value is output.
2
O
2
trim on standby the "Correction value with deactivated controller” specified in parame-
ter 901/902 is output.
3
Controller takes over the neutral correction value,or the updated correction value is output.
4
On expiry of the set lag time, the residual deviation between target and actual value is cor-
rected.
5
firing rate change
O
2
trim is suspended and pre-setting carried out - neutral correction value, or the updated
correction value is output.
6
Control is deactivated, e.g. by a fault
The correction value for deactivated controller specified in parameter 901/902, or the one
specified in parameter 917/918 for ’Air shortage’, is output.
Содержание VMS 4
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...