74
7
Tips and Tricks
7.2
Programming While The Burner Is Running
Pre-purge has been carried out previously without programmed point.
Turn selector switch (1) to SETPOINT
Switch (4) up or down
until system is optimally adjusted at ignition firing-rate
point
control element reacts
display changes
Turn selector switch (1) to ACTUAL VALUE FEED-
BACK
Value of the external feedback (with continuous out-
put) is displayed
with three-point step channel the same value as in
SETPOINT position is displayed
On VMS 5:
Turn selector switch (1) to DISPLAY CHANNEL 5
setpoint and actual value feedback are displayed
Switch (4) (channel 2) up or down until channel 5 is opti-
mally adjusted
Wait until feedback has stopped
Press ENTER (3).
the display shows ’Really ignite?’
Press key (4), to correct the ignition point settings
again.
Press ENTER (3) again.
Burner ignites
The display shows ignition point 1
Содержание VMS 4
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...