32
6
Commissioning
6
Commissioning
6.1
Before Commissioning
6.1.1
Setting the Limit Switches of the Motors
As soon as the VMS is supplied with voltage, it attempts to drive the actuator motors to the
lower limit of the factory set curve. If the end-bearing's limit switches are not properly adjusted
for this, the motor may hit the actuator's mechanical stop
WARNING!
This may damage the motor or the valve.
Therefore:
Check the position of the end-bearing limit switches in the motors, taking into account the mo-
tor output shaft's travel.
If in doubt, set a shorter travel. It may be readjusted later.
6.2
Function Test
Signal on terminal 2 (Burner on) = 0
Control quantity (set point) = minimum. Turn selector
switch (2) to AUTOMATIC.
Apply voltage to VMS:
VMS performs a self-test
The display shows the VMS and its software version
briefly
Compare software version no. with sticker no.
Operating display (5) lights up
Fuel LED (6 or 7) lights up
The four CLOSED LEDs (B) light up
Turn selector switch (1) to status
The display shows BURNER OFF
Turn selector switch (1) to SET POINT
the display shows external regular firing rate input of
200
Содержание VMS 4
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...