121
10
Appendix
Footnotes of the process sequence chart
Legend of the process sequence chart
Any condition
t1
Readiness
t2
Running time, servo actuator
t3
Pre-purge time
t4
Running time, servo actuator
t5
Ignition position
t6
Retardation of the re-circulation damper
t7
Base firing rate
t10
Operating phase
t11
Control mode
t12
Post-purge time (optional)
0 - 255 s, adjustable
*
If the ducts run closed after a shut-off, the pre-purge signal is ignored until they
have reached the lower monitoring threshold.
**
In the absence of the re-circulation signal, the re-circulation dampers remain closed
or run closed (even in pre-purge). The extend to which re-circulation is retarded dur-
ing pre-purge compared to the air damper, can be set via parameter "VODeIR (No.
427) "0".
***
Parameters can be used to select whether the signal is to function as a limit switch
or whether it is always present after ignition.
Содержание VMS 4
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...