63
6
Commissioning
6.7.3
Correction Type 2
NOTICE
This is useful only if curve rises continuously!
WARNING!
Do not use if parts of the curve are horizontal.
WARNING!
When applying O
2
corrections, make sure that the combustion limits are observed even with
the maximum correction applied (100%).
NOTICE
The correction mode indicates how the correction is intended to act. A variety of settings are
possible. Figure 1 and 2 show two typical correction modes for O
2
correction.
Type 1 is used where the correction is made on a linear control element, such as a fan fre-
quency converter. The correction is directly added to or subtracted from the setpoint value.
Type 2 is used where the correction is made on a non-linear control element such as an air
damper. Before determining the correction, account is taken of the steepness of the curve. A
flat curve results in a small correction range, whereas a steep curve give a large range.
If the correction is made to a fuel control element, the effect of the current is reversed, so that
0 mA corresponds to the smallest setpoint.
WARNING!
Do not use if parts of the curve are horizontal.
Содержание VMS 4
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...