129
10
Appendix
10.9
R. P. M. Sensor
10.9.1 Direct Connection to R. P. M. Sensor
(old version delivered up to Sept. 03)
This option allows you to connect an inductive sensor of the company Turck as a speed feed-
back. On this configuration card 3 speed/ pulse ranges can be set at the factory.
Fig. 10-10 R.p.m. sensor 663P8001 delivered up to September 2003
Speed nominal range (164... 819 Digit)
•
I 300 ... 3000 pulses/min (Standard)
•
II 800 ... 4000 pulses/min (Standard)
•
III 1000 ... 8000 pulses/min
Range which is theoretically, technically possible (140-941 Digit)
•
I 200 ... 3500 pulses/min
•
II 680 ... 4600 pulses/min
•
III 740 ... 9310 pulses/min
Only 2 wire NAMUR.
If the set pulse range is exceeded the value remains at the upper end of the range (higher
pulse numbers are ignored).
Below the measuring range the signal goes to 0 (approx. 0 - 7 digit).
CAUTION!
Make sure that the selected measuring range is not exceeded, otherwise speed changes in
excess of this will no longer be detected.
Technical Data
NAMUR input:
Technical Data NAMUR input: U
0
= 8,2 V; Ik = 8,2
mA, +/- 5 %
Make threshold:
max. 2,1 mA (type 1,8 mA)
Break threshold:
max. 1,2 mA (type 1,4 mA)
Linearity error:
< 0,1 % v. E.
Temperature drift:
< 75 ppm/K (type 60 ppm/K)
Содержание VMS 4
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...