Commissioning
3. Press
to display the switch-on parameters and the process reliability.
4. To send the data from the level of the operating unit to the flame scanner, press
.
Alternatively, press
to reject it.
5. Compare the data sent to the flame scanner with the data at the level of the operating unit.
Then:
a) Press
within 8 seconds to save the data. A countdown of 8 seconds begins. This
is accompanied by flashing. During this countdown, you have to confirm the setting by
pressing ENTER. If you do not, an error message appears and the setting is rejected.
b) Alternatively, press
to reject the data.
Icon
Name
Value
Explanation
Switch-on level
0 ... 2,500 mV
Trigger threshold "flame ON"
Fig. 6-18 "Switch-on parameters" display
1
Parameter trigger threshold for flame on
2
Process reliability,
max. fault- useful signal distance
between flame OFF and ON
Switch-on parameters:
Trigger threshold switch-on process
Fig. 6-19 Data sent to the flame scanner
B1
Mode 1
CRC
CRC checksum of the data set
Fig. 6-20 Data received from the flame scanner
Line 1
Data to be sent from the level of the
operating unit
Line 2
Data received by the flame scanner
(flashing)
Содержание F300K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F300K Compact Flame Scanner ...
Страница 2: ......
Страница 26: ...25 5 User Interface 5 2 Menu tree ...
Страница 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Страница 46: ...45 6 Commissioning The data has now been determined and sent to the flame scanner Fig 6 21 Successful transfer ...
Страница 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Страница 122: ...121 14 Appendix ...
Страница 125: ...124 14 Appendix ...