104
14
Appendix
1
The product must not be operated outside the specified range. If it is, any guarantees with regard to safety-related functions lose
their validity.
2
If the critical load is exceeded (e.g. as a result of a contactor load), the specified minimum value is no longer guaranteed. The min-
imum value is important for PLC-type applications.
Input parameters
Supply voltage:
230 VAC +10 %, -15 %
115 VAC +15 %, -15 % (optional)
Can only be done at the factory.
Power consumption:
≤
6 VA
Mains frequency:
45 ... 65 Hz
Allocated fuse in the device, secondary:
315 mA slow-blow
Output parameters
Output no-load voltage
< 33 V
Maximum current drain:
0.25 A
Output contact, safe
Changeover switch (potential-free)
Permissible switching voltage:
1
Max. 250 VAC, 48 VDC
Min. 6 VAC/DC
Permissible switching current:
1
Max. 0.5 A cos
φ
0.4
Min. 10 mA (for a critical load of 50 mA)
2
Allocated fuse in the device:
1
500 mA slow-blow IEC
Output contact, signal contact
Normally open contact (potential-free)
Permissible switching voltage:
1
Max. 250 VAC, 30 VDC, min. 6 VAC/DC
Permissible switching current:
Max. 0.5 A, min. 10 mA (for a critical load of 50 mA)
External fuse protection:
≤
500 mA slow-blow
Connection cross-section
Flexible:
Rapid:
0.5 … 2.5 mm
2
/ 20 AWG ... 13 AWG
0.5 … 4.0 mm
2
/ 20 AWG ... 11 AWG
Extension cable with F300K
Cable length
Maximum extension after 3 m connecting cable:
0.5 mm
2
50 m/ 20 AWG
164,04 ft
1.0 mm
2
100 m/ 17 AWG
328,08 ft
Technical capacity
Mode:
Continuous operation
Safety integrity level:
DIN EN 61508:2011 (SIL 2)
Overvoltage category:
DIN EN 60730-1, ÜKIII
Climatic range
Protection class:
1
FN20: IP20 - following installation, IP40 must be achieved as
a minimum.
FN20-10: IP66
Protection class:
Isolation class II
Содержание F300K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F300K Compact Flame Scanner ...
Страница 2: ......
Страница 26: ...25 5 User Interface 5 2 Menu tree ...
Страница 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Страница 46: ...45 6 Commissioning The data has now been determined and sent to the flame scanner Fig 6 21 Successful transfer ...
Страница 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Страница 122: ...121 14 Appendix ...
Страница 125: ...124 14 Appendix ...