98
14
Appendix
1
The product must not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-
related functions lose their validity.
2
If the critical load is exceeded (e.g. as a result of a contactor load), the specified minimum value is no longer guaranteed. The min-
imum value is important for PLC-type applications.
Input parameters
Spectral ranges
UV-4 - 215 ... 360 nm
UV-4.6 - 215 ... 360 nm
IR-2 - 850 … 1200 nm
IR-3 - 1000 … 1700 nm
IR-4 - 1000 … 2200 nm
UVIR-1 - 215 ... 360 nm
- 1000 … 1700 nm
Output parameters
Flame signal output contact
Normally open contact (potential-free)
Permissible switching voltage
1
Max. 42 VAC/DC
Min. 13 VAC/DC
Permissible switching current
Max. 0.5 A cos
φ
0.4 at
≤
60 °C/+140 °F
Max. 0.4 A cos
φ
0.4 at
≤
80 °C/+176 °F
Min. 10 mA (for a critical load of 50 mA)
2
Provide spark suppression externally for inductive loads,
do not switch capacitive loads.
Fuse protection
Internal self-resetting circuit breaker 900 mA plus fuse 2,5 A
Safety time (FFDT)
Response time in the event of the flame going
out
t
VAus
adjustable via factory password to 1, 2, 3, 4, 5 seconds
(default: 1 second)
Startup delay:
t
VEin
adjustable up to 5 seconds
Output contact stand-by
Normally closed contact (potential-free)
Permissible switching voltage
1
Max. 42 VAC/DC
Min. 13 VAC/DC
Permissible switching current
Max. 0.5 A.
Min. 10 mA (for a critical load of 50 mA)
2
Fuse protection
Required externally
Output parameters
Measuring output for intensity
No galvanic isolation
Output current
Setting range: 4 … 20 mA, 0 … 20 mA
Maximum load
240
Ω
No-load voltage
Approx. 6.5 V
Intrinsic error
± 2 %
Communication
Bus
No galvanic isolation
Driver
High-speed
Speed
500 kbps
Cable length
TP (twisted pair) 80 m/262,46 ft, recommended
Содержание F300K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F300K Compact Flame Scanner ...
Страница 2: ......
Страница 26: ...25 5 User Interface 5 2 Menu tree ...
Страница 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Страница 46: ...45 6 Commissioning The data has now been determined and sent to the flame scanner Fig 6 21 Successful transfer ...
Страница 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Страница 122: ...121 14 Appendix ...
Страница 125: ...124 14 Appendix ...