
76
7
Operation
Sending changed parameter data to the flame scanner
You will find more information on the values in the following table:
NOTICE
Should there be more than 2 devices connected to the BUS (e.g. F300K, FB30), only the last
two devices which are connected to the BUS are allowed to have a BUS terminating resistor.
Press
within 8 seconds.
Icon
Name
Valu
e
Explanation
55:
Intensity 1 –
display
0/1
Category of the flame register’s output when the flame is
OFF for current output and LED chain.
0 = current output and LED chain, always 0 % (default)
1 = current output and LED chain indicate the current
status of the flame signal
56:
Intensity 2 –
LED resolution
0/1
Intensity signal of the LED chain for the flame signal
(only for the F300K without an integrated UI)
0 = low resolution 100 % of LED = default
1 = high resolution 100 % of LED
57:
mA
Current loop 1,
signal type
0/1
0 = display of the flame intensity = default
1 = display of effective value
54:
mA 0/4
Current loop 2,
range
0/4
0 = 0 ... 20 mA (default)
4 = 4 ... 20 mA
59:
2
Bus
termination
0/1
OFF, ON (bus terminating resistor)
1 = default
64:
2 ID
Consec. no. on
bus
1 -
32
Differentiation of different flame scanners on the same
bus
1 = default
Содержание F300K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F300K Compact Flame Scanner ...
Страница 2: ......
Страница 26: ...25 5 User Interface 5 2 Menu tree ...
Страница 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Страница 46: ...45 6 Commissioning The data has now been determined and sent to the flame scanner Fig 6 21 Successful transfer ...
Страница 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Страница 122: ...121 14 Appendix ...
Страница 125: ...124 14 Appendix ...