91
10 Correcting Faults
Two F300K Remote Software programmes have been detected on the bus.
Remove one of the F300K Remote Software programmes from the bus or close it.
C0012 Unknown
device
-
-
Data is received from a device with an unknown device ID.
UI or F300K Remote Software is too old. Update the software.
C0012
C0013
Excess temperature display
-
-
Display switched off because of excess temperature. Communication is not affected.
-
-
Communication error
Learning function errors
No.
Description
Graphic
W *
L1000
Analysis
-
Desired functionality is not yet supported.
X
L1002
Analysis
No valid learning data:
Error during recording:
- Not ready for operation
- Periodicity
- Overload
L1003 Analysis
-
-
No "flame ON" data.
No "flame ON" data learned/recorded.
L1005 Analysis
-
X
Data obtained cannot be used,
Amplitude at "flame on" < amplitude at "flame OFF" (process reliability < 1).
"Flame ON" and "flame OFF" mixed up during learning.
Selected frequency is too high, it can not find a suitable trigger threshold
Note:
Flame scanner testing Device FFP30 does not contain sufficient frequency
components above 100Hz.
Plant requires this state.
L1006
Analysis
-
X
Distance of threshold/level from the limit level too short (process reliability < 1)
Flame with small differences from the background radiation
Unfavourable frequency and/or other parameters selected.
L1007
Analysis
-
X
From F300K SW-Version 1.1 onwards, the evaluation is based on the current present fre-
quency band "S" or "T".
If this is modified after the compilation of the learning data, an evaluation would not be
possible. Reset the frequency band or re-evaluate.
L1008
Analysis
-
X
No evaluable data
Data is not compatible with the SW F300K, learn flames data again.
L1009
Analysis
-
X
Serial number different
Data is not compatible with the SW F300K, learn flames data again.
L1010
Analysis
-
X
Содержание F300K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F300K Compact Flame Scanner ...
Страница 2: ......
Страница 26: ...25 5 User Interface 5 2 Menu tree ...
Страница 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Страница 46: ...45 6 Commissioning The data has now been determined and sent to the flame scanner Fig 6 21 Successful transfer ...
Страница 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Страница 122: ...121 14 Appendix ...
Страница 125: ...124 14 Appendix ...