Page 22
When communicating to the outdoors through horizontal
ducts, each opening shall have a minimum free area
of not less than 1 square inch per 2000 Btu/hr (1100
square mm/kW) of total input rating of all equipment in
the enclosure.
Method 2
: One permanent opening, commencing
within 12” (300mm) of the top of the enclosure, shall
be permitted. The opening shall directly communicate
with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces that
directly communicate with the outdoors and shall have a
minimum free area of 1 square inch per 3000 Btu/hr (734
square mm/kW) of the total input rating of all equipment
located in the enclosure. This opening must not be less
than the sum of the areas of all vent connectors in the
confined space.
Other methods of introducing combustion and ventilation
Combustion Air From Room
In the United States,
the most common requirements specify that the space
shall communicate with the outdoors in accordance
with method 1 or 2, which follow. Where ducts are used,
they shall be of the same cross-sectional area as the
free area of the openings to which they connect.
Method 1
: Two permanent openings, one commencing
within 12” (300mm) of the top and one commencing
within 12” (300mm) of the bottom, of the enclosure
shall be provided. The openings shall communicate
directly, or by ducts, with the outdoors or spaces
that freely communicate with the outdoors. When
directly communicating with the outdoors, or when
communicating to the outdoors through vertical ducts,
each opening shall have a minimum free area of 1
square inch per 4000 Btu/hr (550 square mm/kW) of
total input rating of all equipment in the enclosure.
NOTE: “x”, “xx”, and “xxxx” refer to variations in nominal size. See manufacturer’s catalog for a particular application.
Table 5.
Allowable Single Wall Stainless Steel Vent Suppliers and Part Numbers
Table 6.
Allowable Polypropylene Vent Manufacturers / Trade Names
ALLOWABLE SINGLE WALL STAINLESS STEEL VENT SUPPLIERS AND PART NUMBERS
Selkirk
DuraVent
NovaFlex
Safe-T Vent EZ Seal
FasNSeal
Z Flex
90° Elbow
9x14
FSELB90xx
2SVEExx90
Pipe
9x07
FSVLxxxx
2SVEPxxxx
Boiler Adapter
5x01BOI
FSAAUx
2SVSAxx (OD)
2SVSTTAxx (ID)
Horizontal Termination
(bird screen)
9x92
FSBSx
2SVSTPXxx
Vertical Termination (rain
cap)
5X00CI
FSRCx
2SVSRCxx
Inlet Air Termination
9xTERM
FSAIHXX*
2SVSTEXxx90
Adapter, SS to CPVC
FSA-xxFNSM-xPVCF
Manufacturer Approved
Hanger Straps
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 66'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 3300'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 66'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1122'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 44'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1166'' M
MAAXX..
Adapter SS to PP
FSAAUx-xPP
2ZDCPVCx**
*4", 6" & 7" only
**up to 6"
ALLOWABLE POLYPROPYLENE VENT MANUFACTURERS / TRADE NAMES
CentroTherm
DuraVent
Selkirk
NovaFlex
InnoFlue
PolyPro
PolyFlue
Z-Dens
Single Wall Pipe
ISVLxxxx
xPPS-x
83x002
ZDPx
Elbow
ISELxxxx
xPPS-E90L
83x08
2ZDEx87
PVC Adapter
ISAGLxxxx
xPPS-ADL (to 4")
xPPS-xxPVCM-xPPF (>4")
83x040
2ZDCPVCx
Horizontal Termination
(bird screen)
IASPPxx (2" - 4")
IASSSxx (5" - 12")
xPPS-BG (2" - 6")
83x050
2ZDESx
Vertical Termination
IASPPxx (2" - 4")
IASSSxx (5" - 12")
xPPS-VKL (<5")
xPPS-VTML (5"-8")
83x050
2ZDESx
Air Inlet
2ZDESx
Manufacturer Approved
Hanger Straps
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 33'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 66'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 55'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1100'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 22..55'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1166'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 33'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 66'' M
MAAXX..
MFR MODEL NUMBER (ABBREVIATED)
MFR MODEL NUMBER (ABBREVIATED)
Trade Name / Model
Example Components
Example Components
Trade Name / Model
ALLOWABLE SINGLE WALL STAINLESS STEEL VENT SUPPLIERS AND PART NUMBERS
Selkirk
DuraVent
NovaFlex
Safe-T Vent EZ Seal
FasNSeal
Z Flex
90° Elbow
9x14
FSELB90xx
2SVEExx90
Pipe
9x07
FSVLxxxx
2SVEPxxxx
Boiler Adapter
5x01BOI
FSAAUx
2SVSAxx (OD)
2SVSTTAxx (ID)
Horizontal Termination
(bird screen)
9x92
FSBSx
2SVSTPXxx
Vertical Termination (rain
cap)
5X00CI
FSRCx
2SVSRCxx
Inlet Air Termination
9xTERM
FSAIHXX*
2SVSTEXxx90
Adapter, SS to CPVC
FSA-xxFNSM-xPVCF
Manufacturer Approved
Hanger Straps
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 66'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 3300'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 66'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1122'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 44'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1166'' M
MAAXX..
Adapter SS to PP
FSAAUx-xPP
2ZDCPVCx**
*4", 6" & 7" only
**up to 6"
ALLOWABLE POLYPROPYLENE VENT MANUFACTURERS / TRADE NAMES
CentroTherm
DuraVent
Selkirk
NovaFlex
InnoFlue
PolyPro
PolyFlue
Z-Dens
Single Wall Pipe
ISVLxxxx
xPPS-x
83x002
ZDPx
Elbow
ISELxxxx
xPPS-E90L
83x08
2ZDEx87
PVC Adapter
ISAGLxxxx
xPPS-ADL (to 4")
xPPS-xxPVCM-xPPF (>4")
83x040
2ZDCPVCx
Horizontal Termination
(bird screen)
IASPPxx (2" - 4")
IASSSxx (5" - 12")
xPPS-BG (2" - 6")
83x050
2ZDESx
Vertical Termination
IASPPxx (2" - 4")
IASSSxx (5" - 12")
xPPS-VKL (<5")
xPPS-VTML (5"-8")
83x050
2ZDESx
Air Inlet
2ZDESx
Manufacturer Approved
Hanger Straps
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 33'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 66'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 55'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1100'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 22..55'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 1166'' M
MAAXX..
Distance between Hanger Straps
((H
Hoorriizzoonnttaall RRuunn)) -- 33'' M
MAAXX..
Distance between Hanger Straps
((VVeerrttiiccaall RRuunn)) -- 66'' M
MAAXX..
MFR MODEL NUMBER (ABBREVIATED)
MFR MODEL NUMBER (ABBREVIATED)
Trade Name / Model
Example Components
Example Components
Trade Name / Model
LAARS Heating Systems
Содержание Neotherm NTH
Страница 4: ...LAARS Heating Systems...
Страница 36: ...Page 36 Figure 22 Hydronic Piping Single Boiler Zoning with Circulators LAARS Heating Systems...
Страница 52: ...Page 52 Figure 36 Ladder Diagram 7 H Ladder Diagram LAARS Heating Systems...
Страница 100: ...Page 100 Parts Illustration 4 Internal Components Sizes 750 850 LAARS Heating Systems...
Страница 102: ...Page 102 Parts Illustration 6 Gas Train Components Sizes 600 850 LAARS Heating Systems...
Страница 103: ...Page 103 Parts Illustration 7 Heat Exchanger Components 68A Sizes 285 NEOTHERM Commercial Boilers and Water Heaters...