Figure 33. Power & Control Panel Layout
NOTE: All water heating units are shipped from the factory with a resistor (jumper) between
the outdoor sensor terminals (terminals 1 and 2 on TB7). If this resistor is removed,
the water heater will not be able to heat water above 140°F.
Factory
installed
resistor
LAARS Heating Systems
7.B.2
VARI-PRIME
VARI-PRIME
®
is a variable speed pump controller that is
optional equipment for all commercial NeoTherm boilers.
Pump speed is controlled to maintain a user-chosen
temperature rise between the inlet and outlet of the unit.
VARI-PRIME
®
will operate the boiler pump at maximum
flow during boiler startup to ensure stable operation is
reached before introducing variable water flow. This key
feature keeps the boiler’s combustion and variable speed
pump’s flow in phase with each other, protecting the heat
exchanger from potential low flow conditions.
Contact your manufacturer’s representative for more
details.