Kyland Technology (Shanghai) Co., Ltd PTS-DR200 Time Server
- 29 -
[Figure 3-18] Output Setting Screen (O1)
Table 17 – Output Setting (O1)
Items
Parameters
Description
Output
Signal
PPS1
IRIG-B1
PPM
PPH
Set output signal type for O1.
PPS1: Set output signal is PPS;
IRIG-B1: Set output signal is IRIG-B;
PPM: Set output signal is PPM;
PPH: Set output signal is PPH.
The PPS, PPM and PPH are pulse signal. The interval is per
second, per minute and per hour sending one pulse.
Second
Compensation
0s
Set second compensation offset for O1.
Unit is second(s);
Range is between -999999999s and 999999999s.
Default value is 0s.
When SO-PPS of SO is IRIG-B time signal, the parameter is
also valid for its output signal.
PPS
Compensation
0ns
Set PPS compensation offset for O1.
Unit is nanosecond(ns);
Range is between -250000000ns and 250000000ns.
Default value is 0ns.
When SO-PPS of SO is IRIG-B time signal, the parameter is
also valid for its output signal.