KFU 210- / 410-
6
1.5
Place of installation
In rooms without weather exposure.
Avoid direct insolation.
Avoid dust.
Not in the neighborhood of strong electromagnetic fields.
Not in the neighborhood of inflammable material.
Provide for sufficient cooling. Install a fan if the frequency inverter is installed in a closed electrical
cabinet.
Altitude of installation: ≤ 4000 m, above 1000 m with reduced power (reduced output current).
Ingress protection rating of frequency inverter: IP20.
The frequency inverter produces noise. For this reason it should be installed in areas where people
normally don't stay.
Noise emission in operation is < 85 dB(A) in the case of sizes 1 through 7.
Noise emission in operation is approx. 86 dB(A) in the case of size 8. Ear protectors must be used when
staying near the frequency inverter
Use of the device in explosive atmospheres is not permitted.
1.6
Operation conditions
Size 1…7:
Ambient temperature: 0…55°C, as from 40°C, power reduction of 2.5% / K should be considered.
Size 8
Ambient temperature: -25…55°C, as from 45°C, power reduction of 2.5% / K should be considered.
Relative humidity: 5 ... 85%, no water condensation
Ambient pressure: 70 ... 106 kPa to be checked
The frequency inverter may be operated in TN, TT and IT grid types.
Operation in a corner-grounded TN grid shall not be permissible.
Environment specification: Pollution degree 2 and overvoltage category III (IEC 60664-1 /DIN VDE 0110-
1).
The frequency inverter may be connected to power supply every 60 s. If the unit is switched on more
frequently, it may be damaged. This must be considered when operating a mains contactor in jog
operation mode.
Max. permissible expected short circuit current at mains connection:
up to 132 kW device power (Size 7): 5 kA;
160…250 kW device power (size 8): 18 kA
as from 315 kW device power (size 8): 30 kA