KFU 210- / 410-
40
Error messages
Key
Meaning
F00
00
No fault has occurred.
Overload
F01
02
Frequency inverter overloaded (60 s), check load behavior
03
Short-term overload (1 s), check motor and application parameters
Heat sink
F02
00
Heat sink temperature too high, check cooling system and fan.
01
Temperature sensor defective or ambient temperature too low.
Interior
F03
00
Interior temperature too high, check cooling system and fan.
01
Interior temperature too low, check control cabinet heating.
Motor connection
F04
00
Motor temperature too high or sensor defective, check connection S6IND.
03
Phase failure, check motor and wiring.
Output current
F05
00
Overloaded, check load situation and ramps.
03
Short circuit or earth fault, check motor and wiring.
05
Asymmetric motor current, check current and wiring.
06
Motor phase current too high, check motor and wiring.
07
Message from phase monitoring, check motor and wiring.
DC-Link voltage
F07
00
DC link voltage too high, check deceleration ramps and connected brake resistor.
01
DC link voltage too low, check mains voltage.
02
Mains failure, check mains voltage and circuit.
03
Phase failure, check mains fuse and circuit.
04
Mains voltage UDC too high when turned on, check voltage.
05
Mains voltage BC too high when turned on, check voltage.
06
Mains voltage MC too high when turned on, check voltage.
Electronic voltage
F08
01
Electronics voltage too low, check control terminals.
04
Electronic voltage too high, check wiring of control terminals.
Output frequency
F11
00
Output frequency too high, check control signals and settings.
01
Max. frequency reached by control (voltage control), check deceleration ramps and connected
brake resistor