4.2.1 Control terminals X210A and X210B
1
Control terminals are freely configurable
Control terminal X210A
X210A.1 Voltage output DC +20 V or input for external
power supply DC 24 V ±10%
X210A.2 GND 20 V/ GND 24 V (ext.)
X210A.3 Digital input STOA (first shut-down path)
X210A.4 Digital input
1)
Start clockwise
(default setting.)
X210A.5 Digital input
1)
Start anticlockwise
(default set..)
X210A.6 Digital input
1)
Data Set Changeover. 1
(default.)
X210A.7 Digital input
1)
Data Set Changeover. 2
(default)
Control terminal X210B
X210B.1 Digital input
1
)
X210B.2 Digital input STOB (second shut-down path)
X210B.3 S1OUT: Digital output
)
X210B.4 Multifunktion output
1
)
(voltage signal pro
portional actual frequency, default setting)
X210B.5 Supply voltage DC +10 V for reference value
potentiometer, (I
max
=4 mA)
X210B.6 Multifunction input
1)
(reference speed 0 …
+10 V, default setting)
X210B.7 Ground 10 V
Relay output X10
S3OUT
Parameterizable relay output
Control “Safe Torque Off” (STO): Contacts on X210A.3 and X210B.2 open (“Low level”).
Release of frequency inverter: Contacts on X210A.3 and X210B.2 closed (“High level”).
The above assignment of the functions to the control terminals is the default setting of parameter Con-
figuration 30 to value 110 or 410. The functions can be assigned to the control terminals as required.
For more configurations, refer to the Operating Instructions.