KFU 210- / 410-
31
Further machine data are measured while the drive is at a standstill. These
measurements will be entered automatically in the relevant parameters by the parameter
identification feature.
Confirm the display "PAidE" by pressing the ENT key.
Note the warnings or error messages upon completion of the parameter identification.
No signals at digital inputs S1IND (STOA) and S7IND (STOB). If signals were already
applied at the beginning of the guided commissioning, the "StO" message is not
displayed.
For release of the output stage, wiring of digital inputs S1IND (STOA) and S7IND (STOB) is required.
Confirm the final "rEAdY" message by pressing the ENT key.
Canceling the operation with the ESC key or withdrawing the enable signal S1IND
(STOA) or S7IND (STOP) results in an incomplete take-over of the values.
In the case of higher requirements as regards the accuracy of the speed/torque control, you should
carry out the guided commissioning procedure once again under operating conditions because part of
the machine data depends on the operating temperature.
During this procedure, confirm the rated machine values already entered.
Confirm the "End" display by pressing the ENT key.
The guided commissioning of the frequency inverter is terminated via a reset and the
initialization of the frequency inverter. The relay output X10 signals a fault.
After successful initialization of the frequency inverter, the factory-set parameter Actual
Frequency 241 is displayed.
The drive is accelerated to the set Min. frequency 418 (default 3.50 Hz) by:
Signals at digital inputs S1IND (STOA) and S7IND (STOB) and
Start clockwise by rising signal edge at S2IND or
Start anticlockwise by rising signal
edge at S3IND