4 Electrical installation
DANGER
!
The five safety rules must be complied with.
Disconnect the frequency inverter from mains voltage (AC and DC) and protect it against
being energized unintentionally.
Verify safe isolation from power supply.
When the frequency inverter is disconnected from power supply, the mains, DC-link voltage
and motor terminals may still be live for some time. Wait for some minutes until the DC link
capacitors have discharged before starting to work at the unit.
Sizes 1 through 7 (up to 132 kW): The DC-link may have dangerous voltage levels even up to
3 minutes after shutdown.
Size 8 (as from 160 kW): The DC-link may have dangerous voltage levels even up to 10
minutes after shutdown.
Switch off power supply before connecting or disconnecting the mains cables to/from terminal
X1, and the motor cables and braking resistor to X2.
NOTE
The cables connected to the frequency inverters may not be subjected to high-voltage
insulation tests.
Use copper cables designed for an ambient temperature of at least 30 °C.
In the case of UL/CSA installations: Only use 75°C copper cables.
The earth leakage current of the frequency inverter may exceed AC 3.5 mA or DC 10 mA.
NOTE
Please note (according to EN61800-5-1):
This product may cause direct current in the protective earth conductor. Where residual
current de-vices (RCD) or residual current monitors (RCM) are used as a protection against
direct or indirect contact, only RCDs / RCMs of Type B are permissible on the power supply
side of this product.