KFU 210- / 410-
41
Safety fuction STO
F12
01
Diagnosis error of function STO; at least one of the shut-down paths STOA and STOB is defective.
Check the devices connected to the shut-down paths; check wiring and EMC.
04
Software self-diagnosis has detected an internal error. Parameter Error Environment 1 262
describes the cause of the error.. Consult Küenle customer service.
05
Fault message of 5-second monitoring. Shut-down paths STOA and STOB were not actuated at
the same time, but with an offset of more than 5 seconds. Check addressing of shut-down paths or
control of protection provision.
Motor connection
F13
00
Earth fault at output, check filter and cabling.
10
Minimum current monitoring, check motor and wiring.
Control connection
F14
01
Reference value on multifunction input 1 faulty, check signal.
07
Overcurrent on multifunction input 1, check signal.
7.2
Status messages during commissioning (SS…)
The following status messages are possible when Setup is run:
Status message
Meaning
SS000 OK
Auto set-up routine has been carried out.
SS001 PC Phase 1
The plausibility check (PC) of the motor data is active.
SS002 PC Phase 2
The calculation of dependent parameters is active.
SS003 STO
The parameter identification requires release on digital input STOA and STOB.
SS004 Parameter
identification
The rated motor values are checked by the parameter identification feature.
SS010 Setup already active
The setup routine via the control panel is being carried out.
SS030 No Release
The parameter identification demands the controller release on digital input
STOA and STOB.
SS031 Error – check P. 259
Error during the auto set-up routine. Check value of Current Error 259.
SS032 Warning Phase
Asymmetry
The parameter identification feature diagnosed an unbalance during the
measurements in the three motor phases.
SS099 Setup not carried out
yet.
Self-setup has not yet been carried out.