KFU 210- / 410-
39
7 Control unit messages
Status indication
LED
green
red
Display
Description
Rotary field on motor
off
off
-
no supply voltage
no
on
on
-
initialization and self-test
no
flashing off
RUN flashing
ready, no output signal
no
on
off
RUN
operating message
yes
on
flashing RUN + WARN
Operational message, current Warning 269
yes
flashing flashing RUN + WARN
Ready for operation, current Warning 269
no
off
flashing FAULT flashing Current Error 259 of frequency inverter
no
off
on
FAULT
Current Error 259, acknowledge fault
no
7.1
Warning and error messages during operation
The code displayed via parameter Warnings 269 can be composed of several messages.
Key A0088 signals warnings A0008 + A0080, for example.
Warning messages
Key
Meaning
A0000
No warning present.
A0001
Frequency inverter overloaded, warning code (A0002 or A0004)
A0002
Frequency inverter overload (60 s). Check load behavior.
A0004
Short-term overload (1 s). Check motor and application parameters.
A0008
Max. heat sink temperature reached, check cooling system and fan.
A0010
Max. interior temperature reached, check cooling system and fan.
A0020
Speed set point is limited by a controller.
A0080
Max. motor temperature reached, check motor and sensor.
A0100
Mains phase failure, check mains fuses and supply cable.
A0400
Limit frequency reached; output frequency is limited.
A4000
DC link voltage has reached the type-specific minimum.
A8000
Application-specific warning: For detailed functions, refer to Operating Instructions.
Current Error 259 and Last Error 310 make troubleshooting easier, an error code is
displayed.
The error message can be acknowledged via the control unit buttons and STO input.