7 Servicing/Maintenance
73 of 126
Amacan K
1579.807/07-EN
7.7.2 Installing the replacement cable gland
81-97
82-11/
68-3.02
914.04
834.01
412.07
812
412.08
834.02
914.05
81-29.03
81-18.03
901.20
932.20
L
243
L
243
Fig. 40:
Installing the cable gland
Table 24:
Symbols key
Symbol
Description
L
243
Always secure screwed connections marked with this symbol with
Loctite 243
.
Installing the power cable
ü
The motor housing cover has been removed, placed down and protected against
rolling off.
1. Adjust the lengths of the cable cores to the original cable gland.
2. Attach the core identification to match the original cable gland.
3. Slide O-ring 412.07 onto the core ends of the power cable and into the groove
of the centring seat.
4. Insert cable gland 834.01 with the power cable and O-ring 412.07 into the
opening provided.
5. Fasten cable gland 834.01 with hexagon socket head cap screws 914.04. Secure
the screwed connection with Loctite 243.
6. Fit cable terminals to the core ends of the power cable.
7. Fasten the earth conductor (green/yellow) to the inside of the motor housing
cover 812 with bolt 901.20 and spring washer 932.20.
8. If shielded cables are used, connect the shield to terminal 81-29.03 on the inside
of motor housing cover 812.
Installing the control cable
ü
The motor housing cover has been removed, placed down and protected against
rolling off.
1. Adjust the lengths of the cable cores to the original cable gland.
2. Attach the core identification to match the original cable gland.
3. Guide O-ring 412.08 onto the short core ends of the control cable and into the
groove of the centring seat.
4. Insert cable gland 834.02 with the control cable and O-ring 412.08 into the
opening provided.