5 Installation at Site
31 of 126
Amacan K
1579.807/07-EN
Fig. 15:
Lowering the pump set
18. Finally, attach the support rope with shackle and turnbuckle to a suspension
loop (provided in the discharge tube or structure). Secure the turnbuckle with a
split pin. After inserting the split pin, bend over its two legs.
19. Tighten the turnbuckle until the cables are tight but do not lift the pump off its
seat.
20. Unclip the hook of the lifting equipment from the lifting lug, free the cables
from the manila rope and route them to the control cabinet.
21. Make sure that the top loose lifting lug is attached to the cable bundle to
prevent noise and wear caused by chafing.
22. Remove the safety cover from the discharge tube and mount the discharge tube
cover. Seal the cable entries if any!
5.3.3 Installing the pump set with a support rope and support spacer
Refer to and comply with the general arrangement drawing/outline drawing when
installing the pump set.
Prior to installing the pump set, visually inspect the support rope. Do not exceed the
permissible load-carrying capacity.