WARNING
When installing the device obligatorily place expansion vessel into the system.
WARNING
Obligatorily install safety valve onto the inflow pipe, which has a nominal
pressure of 0,6 MPa (6 bar), and prevents the increase of pressure in the hot
water storage for over 0,1 MPa (1 bar) above nominal.
WARNING
For proper operation of expansion vessel, a suitable setting of the operational
pressure of the tank must be made. The pressure is set in regards to the
pressure in the plumbing. The setting needs to be checked every 6 months..
5.4 Air Canal Installation
The device has attachments on left and right for the attachment of air canals, which enables:
the placement of the device into any room which is spacious enough
ventilation of desired room
exhaust of waste air or intake of fresh air from the environment
In the case of air canal use, keep in mind that air pipes and every additional knee represent
additional air resistance and lesser capacity of the device. Table 1 shows maximal permitted
canal lengths. Air canals must be isolated to prevent water condensation on the pipe
surfaces.
Figure 8 shows the device with air canal connections. The connections are 45 mm in length
and an outside diameter of
Φ250. Access to inner parts is protected with mesh.
Figure 8: Air canal connection
Table 1: Maximal permitted air canal length.
Air canal diameter
Maximal air canal length
Diameter 200 mm
10 m
Diameter 250 mm
15 m
The final length of air canals needs to take into consideration also the equivalent length of
accessories such as knees, reduction pieces, etc.