- Make sure that the switch on the connecting cable from
the gas
control module with the receiver is set to „I”.
(Option)
- Check that the cable connecting the receiver to the gas
control module is not damaged.
- If the stepper motor is not working properly, replace the
gas control module.
- If the coil of the gas control unit is not working properly
replace the module.
- If the micro-switch of the gas control module is not
working properly, replace the module
No spark at the electrode
✓
Check the cable connection between the receiver and the
electrode.
✓
Check that the electrode is not damaged.
✓
Check the operation of the sparker.
✓
Check that there is no system breakdown.
✓
If the ignition components are working properly and the
firing procedure does not start:
-
Press the „RESET” button on the receiver.
- If it is possible, shorten the cable between the receiver and
the electrode.
- Add a grounding cable between the controller and the
control burner.
No control flame
✓
Make sure that the gas shut-off valve is open.
✓
Repeatedly make attempts to ignite the fireplace.
✓
Check that the pressure in the gas installation is
appropriate.
✓
Check the connection between the breaker and the
receiver.
After lighting the control
flame, spark still appears
at the electrode
✓
Check the connection between the breaker and the
controller.
✓
In the case of damage to the electronic amplifier, replace
the receiver.
The control flame
extinguishes
automatically
✓
Make sure the thermocouple sensor is operating and
✓
Properly connected to the gas control module.
✓
Make sure the flame control is capable of heating the temp.
sensor.
✓
Check that the gas valve of the gas control module is not
damaged.
Weak control flame
✓
Check the gas pressure in the control flame.
✓
Check if draft reductor is mounted properly.