HEARTH REQUIREMENTS FOR FLOOR PROTECTION
This fireplace requires a non-combustible floor protection made of tile, marble, bricks or other non-
combustible material minimum 2 inches thick, that does not extending over the bottom grid. (Hearth
must be under the bottom grid).
Figure 5. Scheme of floor protection and grids installation.
PLEASE NOTE
that the floor protection should extend for at least 39-inches of the front and both sides
of the unit unless the floor and the walls are non-combustible. This appliance must be placed on
noncombustible, concrete floor.
The bottom air inlet grid shall be placed dunder the screen and at least 2 inches above the floor. Please
left as much space as needed for accommodation of the grid.
MANTELS
Because of the extreme heat this fireplace emits, any mantel to be used with this fireplace has to be
non-combustible. Any combustible materials are not approved to be used during the installation of
this fireplace