ADJUSTMENT 

43

11.0  ADJUSTMENT

11.1  Pressure Testing

NOTE: The appliance and its appliance main gas valve must be 

disconnected from the gas supply piping system during any pressure 

testing of the system at test pressures in excess of ½ psi (3.5 kPa). 
IMPORTANT: Pressure check taps for manifold (outgoing) and inlet 

(incoming) pressure have been incorporated into the valve. The 

pressure tap marked OUT measures outgoing pressure. The pressure 

tap marked IN measures incoming pressure. 

11.1.1  Inlet Pressure Test

NOTE: Make sure to apply these incoming pressure test with all other 

gas appliances on, or at full capacity in the house for proper pressure 

reading.
IMPORTANT: If the inlet pressure reading is too high or too low, contact 

the gas company. Only a qualified gas service technician should adjust 

incoming gas pressure. 

1.  Loosen the inlet (IN) pressure tap by turning screw counter-

clockwise. See (A) in Figure 11.1.

2.  Attach manometer using a ¼ in (6 mm) I.D. hose.
3.  Light pilot and burner. Check pressure to ensure it is between 

the minimum and maximum recommended pressure settings.

4.  Turn off burner and pilot.
5.  Disconnect hose and tighten the inlet (IN) pressure tap by 

turning screw clockwise. Screw should be snug. Do not over 

tighten.

6.  Relight pilot and burner. Then reattach manometer to the 

inlet pressure tap (A) to verify the tap is completely sealed. 

Manometer should read no pressure.

11.1.2  Manifold Pressure Test

1.  Light pilot.
2.  Loosen manifold (OUT) pressure tap by turning screw counter-

clockwise. See (B) in Figure 11.1.

3.  Attach manometer to pressure tap using a ¼ in (6 mm) I.D. hose.
4.  Light burner. Check manometer reading.
5.  Turn burner and pilot off.
6.  Disconnect manometer hose and tighten the manifold (OUT) 

pressure tap by turning screw clockwise. Screw should be snug. 

Do not over tighten.

7.  Attach the manometer to the manifold pressure tap (B) to verify 

it is completely sealed. The manometer should read no pressure 

when pilot and burner are on.

Table 11.1, Inlet Pressures

Fuel

Natural Gas

Propane

Gas Supply

Min - Max

Min - Max

Inlet Pressure 

Tap (A)

5” - 10.5” WC 

(1.25 - 2.62 kPa)

12” - 13” WC 

(2.99 - 3.24 kPa)

Table 11.2, Manifold Pressure

Fuel

Natural Gas

Propane

Gas Supply

Low - High

Low - High

Manifold Pressure 

Tap (B)

1.0” - 3.5” WC

(.25 - .87 kPa)

2.7” - 10” WC

(.67 - 2.49 kPa)

Figure 11.1, Pressure Check Taps

Inlet pressure tap

Manifold pressure tap

Содержание SLA-60

Страница 1: ...ome USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other g...

Страница 2: ......

Страница 3: ...ty but also customer safety We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong President Dudley Hussong Boa...

Страница 4: ......

Страница 5: ...Clearances 24 7 0 VENTING 25 7 1 Approved Vent Systems 25 7 2 Venting Requirements 25 7 3 Elbows 25 7 4 Restrictor Plate Assembly and Installation 25 7 5 Vertical Terminations 26 7 6 Combination Vent...

Страница 6: ......

Страница 7: ...eriod a battery operated carbon monoxide detector with an alarm shall be installed 1 3 2 Approved Carbon Monoxide Detectors Each carbon monoxide detector as required in accordance with the above provi...

Страница 8: ...Installation Code local authorities or codes having jurisdiction in you area regarding derate guidelines 2 1 1 1 US Installations Refer to the American Gas Association guidelines for the gas designed...

Страница 9: ...60 R 8 March 2022 Hussong Mfg Co Inc Kozy Heat Fireplaces SPECIFICATIONS 9 2 3 Appliance Dimensions TOP FRONT LEFT SIDE RIGHT SIDE GAS LINE HOLE GAS LINE HOLE ELECTRICAL ACCESS Figure 2 1 SLA 60 Dimen...

Страница 10: ...rim kit assembly for use only with safety barrier SL60 RSF will allow you to install finishing material up to the finishing edge Refer to Section 4 2 Optional Trim Kit Assembly SL60 FTK on page 21 The...

Страница 11: ...5 in 147 mm minimum clearance to the header Use only non combustible material in this area for the entire width of the fireplace DO NOT use wood sheetrock et cetera in this zone Top stand off brackets...

Страница 12: ...replace with the stand off flanges on the nailing flanges facing away from the fireplace 3 Secure the nailing flanges to the fireplace with screws provided through the slots in nailing flanges 4 Bend...

Страница 13: ...ombustibles Table 3 1 Minimum Appliance Clearances to Combustible Material From appliance top stand offs 0 in 0 mm From appliance left and right side stand offs 0 in 0 mm From appliance back stand off...

Страница 14: ...on carpeting tile or other combustible material other than wood flooring this appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance This fireplace m...

Страница 15: ...must be used This will increase the minimum heightforthecenteroftheventpipeby3 1 4 83mm whenframing the wall pass through NOTE Kozy Heat s 800 WPT3 or wall thimble products that comply with the requi...

Страница 16: ...outdoor covered fireplace installation allows a fireplace to be installed in an outdoor covered area where the appliance is protected from direct precipitation Follow the instructions and illustration...

Страница 17: ...A T H E R P R O O F O V E R H A N G I N F R O N T A N D S I D E S MINIMUM WEATHERPROOF OVERHANG IN FRONT AND SIDES M I N I M U M W E A T H E R P R O O F O V E R H A N G I N F R O N T A N D S I D E S F...

Страница 18: ...e This fireplace is designed to accommodate non combustible facing material up to 1 2 in 13mm thick Install facing material up to the finishing edge that surrounds the glass frame assembly Do not appl...

Страница 19: ...o Inc Kozy Heat Fireplaces FACING AND FINISHING 19 17 483mm 14 362mm 40 1022mm 313 16 792mm 62 1581mm EACH SQUARE REPRESENTS 1 25mm OF MANTEL PROJECTION FINISHING EDGE COMBUSTIBLE FLOORING 12 305mm 9...

Страница 20: ...TERIAL ALLOWED COMBUSTIBLE MATERIAL ALLOWED NO SCREWS ABOVE FRAMING LOWER COVER PANEL COMBUSTIBLE MATERIAL ALLOWED NO SCREWS ABOVE FRAMING BOTTOM 19mm 63 1600mm 11 292mm 19mm 5 140mm 87 8 225mm 617 16...

Страница 21: ...frame assembly There are 5 holes above and 5 holes below the fireplace opening and 3 holes on each side 2 Align the top and bottom trim panels with the pre drilled holes on the fireplace face Positio...

Страница 22: ...3 5 kPa For test pressures equal to or less than psi 3 5 kPa the appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve A listed and Commonwealth...

Страница 23: ...30 Over 6 12 to 7 12 1 25 0 38 Over 7 12 to 8 12 1 5 0 46 Over 8 12 to 9 12 2 0 0 61 Over 9 12 to 10 12 2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 0 1 22 Over 12 12 to 14 12 5 0 1 52...

Страница 24: ...building or the combustion air inlet to any other appliance 12 in 30 cm 9 in 23 cm K Clearance to mechanical air supply inlet 6 ft 1 83 m 3 ft 91 cm above if within 10 ft 3 m horizontally Massachuset...

Страница 25: ...red 1 in 25 mm clearance to combustibles must be installed for all horizontal vent runs that pass through interior or exterior walls These wall thimble products may be insulated using unfaced insulati...

Страница 26: ...listed as non combustible per ASTM E 136 Table 7 1 NG Propane Minimum Maximum Vertical Terminations Minimum Vertical Length Maximum Vertical Length 3 ft 914 mm 50 ft 15 2 m Minimum Maximum Vertical V...

Страница 27: ...al Vent Pipe Minimum Horizontal Vent Pipe Maximum Horizontal Run 12 in 6 in 305mm 152mm 9 in 229 mm 36 in 914 mm Minimum Vertical Vent Pipe Min Max Horizontal Terminations 12 6 305mm 152mm minimum ver...

Страница 28: ...tical Vent Pipe Minimum Horizontal Vent Pipe Maximum Horizontal Run 24 in 610 mm 9 in 229 mm 24 in 610 mm Minimum Vertical Vent Pipe Min Max Horizontal Terminations 24 610mm vertical vent pipe 90 hori...

Страница 29: ...overlap a minimum of 1 1 2 38mm Secure to exterior wall with 4 screws not provided 7 7 2 Vent Assembly and Installation 1 Mount the required 800 WPT3 G or a wall thimble that complies with the require...

Страница 30: ...the fireplace 3 Secure the vertical vent heat shield to the fireplace with 2 attachment screws provided in the components package 7 8 2 Minimum Horizontal Venting 1 Bend perforation on the 3 hand tab...

Страница 31: ...the firebox while lowering the bottom of the glass assembly into position 2 Pull the spring loaded latches out and up to secure the bottom of glass to the bottom of the fireplace 3 Reinstall valve acc...

Страница 32: ...Remove 75 of the crushed glass covering the burner ports Do not block the pilot assembly 4 Save any unused media for later use 8 3 3 311 Series Glass Media Installation 1 Remove glass media from its p...

Страница 33: ...ove assembly from firebox 10 Remove and save 12 screws securing the control board 11 Lift the control board out of the firebox being careful not to damage sealing gasket underneath 8 4 2 Control Board...

Страница 34: ...must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 9 2 Wiring Requir...

Страница 35: ...4 When the motor end clears the fireplace face turn the fan to the left FIGURE 9 2 5 Rotate the top end down and to the right lowering the fan into control compartment FIGURE 9 3 6 Position fan as sho...

Страница 36: ...nce 10 Press the wireless remote POWER button 11 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier OPERATING INSTR...

Страница 37: ...e will operate on the backup battery pack in a power outage The lifespan of the backup batteries depends on various factors such as the quality of the batteries number of ignitions etc There is a cut...

Страница 38: ...TE switch to ON The control module will illuminate a green LED 2 times and emit a beep The ignition sequence will start again 10 7 Additional Diagnostic Information Diagnostic codes are outlined below...

Страница 39: ...control will go into a standby mode if no buttons are pressed within 5 minutes Press the POWER button to reactivate the remote control to ON mode Active functions will be displayed once in ON mode PO...

Страница 40: ...e beep will confirm the reception of the command 10 8 7 Pilot Ignition Selection Intermittent or Pilot on Demand This system has the option of a pilot on demand allowing the system to change from a sp...

Страница 41: ...the room temperature drops below the set temperature 10 8 10 Fan Speed Control optional The fan speed can be adjust through 3 speeds HIGH MEDIUM LOW The fan is controlled by a timer built into the con...

Страница 42: ...in increments of 15 30 45 60 90 120 and 180 minutes To activate this function 1 Press the MENU button to activate the menu 2 Using the UP and DOWN arrows highlight the TIMER icon and press SELECT 3 Us...

Страница 43: ...nimum and maximum recommended pressure settings 4 Turn off burner and pilot 5 Disconnect hose and tighten the inlet IN pressure tap by turning screw clockwise Screw should be snug Do not over tighten...

Страница 44: ...rientation closing the air shutter will achieve a desired yellow flame but may produce soot on the glass Opening the air shutter will cause a short blue flame that may lift off the burner 11 2 1 1 Ven...

Страница 45: ...r installing and verifying correct vent installation shut off the gas supply and call a qualified service technician 11 2 2 1 Restrictor Plate Installation 1 Remove the safety barrier and the glass fr...

Страница 46: ...nnection Ensure batteries are fully charged if using battery back up as power source Use wiring schematic to determine that all wiring connections are secure and correct Control module selector switch...

Страница 47: ...ered ON and thermostat operation is turned OFF Pilot and burner extinguish while in operation No Propane in tank Check propane tank Refill if necessary Incorrect glass assembly installation Refer to S...

Страница 48: ...em Check the vent pipes for leaks and the vent cap for debris Repair the vent pipes or remove debris from vent cap if necessary No reaction to command Battery back up batteries or remote control batte...

Страница 49: ...tructions provided with installation Refer to Section 7 0 Venting on page 25 Performed by Qualified Service Person Frequency Annually Action Examination of the vent system is required The flow of comb...

Страница 50: ...f the flame safety system Pilot or Flame rectification device Visually check pilot light when in operation Inspect and ensure the lighting of the main burner occurs within 4 seconds of the main gas va...

Страница 51: ...Natural Gas DEX 192 Conversion Kit Natural Gas NCK SL60 D Pilot Assembly Propane DEX 192 1 Conversion Kit Propane LCK SL60 D Dexen Transmitter Remote Control DEX RC3 Center Burner Tube SL60 C035 Pilot...

Страница 52: ...but not limited to improper chimney venting installation will also render this warranty void 7 This warranty does not cover installation and operational related problems such as environmental conditio...

Страница 53: ......

Отзывы: