28
VENTING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
#SLA-60 R.8 March 2022
7.6.2 Propane Installations
IMPORTANT: The vertical vent heat shield included with this fireplace
must be installed for all venting configurations. The horizontal vent
heat shield must be installed when incorporating minimum horizontal
venting. Refer to 7.8 on page 30.
IMPORTANT: Horizontal vent sections require ¼ in (6 mm) rise for every
12 in (305 mm) of travel.
Table 7.4, Propane - Minimum Horizontal Vent Terminations
Minimum
Vertical Vent Pipe
Minimum
Horizontal Vent Pipe
Maximum
Horizontal Run
24 in
610 mm
9 in
229 mm
24 in
610 mm
Minimum Vertical Vent Pipe, Min. / Max. Horizontal Terminations:
24” (610mm) vertical vent pipe + 90° horizontal elbow + 9” (229mm)
minimum horizontal vent pipe / 24” (610mm) maximum horizontal
run + termination cap
Table 7.5, Propane- Max Vertical / Max Horizontal Combination
Maximum
Vertical Rise
Maximum
Horizontal Run
Total Length
25 ft
7.6 m
25 ft
7.6 m
50 ft
15.2 m
Maximum number of 90° elbows: 5
DIAG.3 PROPANE MINIMUM HORIZONTAL VENTING
(A)
Stand-off Brackets
(B)
Stand-off Heat Shields
(C)
90
°
Elbow
(D)
Vertical Vent Heat Shield
(E)
Horizontal Vent Heat Shield
(F)
Termination Cap
Figure 7.3, Propane Combination Venting